The following protection functions are automatically blocked in the case of a measuring-voltage failure:
•
Distance protection
•
Directional negative-sequence protection
•
Ground-fault protection for high-resistance faults in grounded-neutral systems
Structure of the Function
The function is part of protection function groups which are connected with a 3-phase voltage and current
measurement point.
[dwstrffm-210113-01.tif, 1, en_US]
Figure 9-4
Structure/Embedding of the Function
The function is broken down into 3 subfunctions (see
):
•
Supervision for unbalanced measuring-voltage failure
•
Supervision for 3-phase measuring-voltage failure
•
Supervision for switching onto a 3-phase measuring-voltage failure
[lozusamm-100611-01.tif, 2, en_US]
Figure 9-5
Breakdown of the Measuring-Voltage Failure Detection Function
Each subfunction creates its own monitoring indication. The function summarizes these indications via the
group indication
Alarm
.
The response to the detection of a measuring-voltage failure is explained in the specific protection-function
descriptions.
9.3.2.2
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1245
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...