7SG14 Duobias-M-200 Commissioning
©2010 Siemens Protection Devices Limited
Chapter 7 Page 20 of 20
1.5 Trip, Alarm and Indication Tests
T
EST
A
CTION
R
ESULT
Trip/Intertrip
Local and Remote CB Trip Operation
Confirmed
OK
Remote Alarms
All external Alarms confirmed
OK
LED Indication for operation of
external protection
All LED’s correctly indicate for the
operation of each device
OK
Protection Healthy
Alarm
Local (and Remote) indication
and alarm confirmed
OK
Table 18 - Trip, Alarm and Indication Test
1.6 Communication
T
EST
A
CTION
R
ESULT
Local Relay Port
Download Settings Confirmed
OK
Saved Settings File
Record the name of the As Installed
Settings File(s) and storage location
Remote Relay Access(if used)
Relay Access Confirmed
OK
Relay Password
Enter Password(NONE is entered if not
used)
OK
Numeric Password Code
_ _ _ _ _ _ _ _ _ _ _ _
Record Password Code
Table 19 - Communication