7SG14 Duobias-M-200 Commissioning
1.2.2 Output Relays
O
UTPUT
R
ELAY
(L
OCATION
)
T
YPE
T
ERMINAL
N
O
.
U
SED
I
N
S
CHEME
C
HECKED
Relay 1(PSU)
C/O 4
(NO)
5 (COM)
6 (NC)
OK
Relay 2(PSU)
C/O 9
(NO)
8 (COM)
7 (NC)
OK
Relay 3(PSU)
C/O 10
(NO)
11 (COM)
12 (NC)
OK
Relay 4 (PSU)
N/O 17
–19
OK
Relay 5 (PSU)
N/O
18 – 20
OK
Relay 6 (I/O 1)
N/O 2-4
OK
Relay 7 (I/O 1)
N/O 6-8
OK
Relay 8 (I/O 1)
N/O 10-12
OK
Relay 9 (I/O 1)
N/O 14-16
OK
Relay 10 (I/O 1)
N/O 18-22
OK
Relay 11 (I/O 1)
N/O 20-22
OK
Relay 12 (I/O 1)
N/O 24-28
OK
Relay 13 (I/O 1)
N/O 26-28
OK
Relay 14 (I/O 2)
N/O 2-4
OK
Relay 15 (I/O 2)
N/O 6-8
OK
Relay 16 (I/O 2)
N/O 10-12
OK
Relay 17 (I/O 2)
N/O 14-16
OK
Relay 18 (I/O 2)
N/O 18-22
OK
Relay 19 (I/O 2)
N/O 20-22
OK
Relay 20 (I/O 2)
N/O 24-28
OK
Relay 21 (I/O 2)
N/O 26-28
OK
Relay 22 (I/O 3)
N/O 2-4
OK
Relay 23 (I/O 3)
N/O 6-8
OK
Relay 24 (I/O 3)
N/O 10-12
OK
Relay 25 (I/O 3)
N/O 14-16
OK
Relay 26 (I/O 3)
N/O 18-22
OK
Relay 27 (I/O 3)
N/O 20-22
OK
Relay 28 (I/O 3)
N/O 24-28
OK
Relay 29 (I/O 2)
N/O 26-28
OK
Table 3 - Output Relay Contacts
1.3 Secondary Injection
1.3.1 Accuracy of Measurement
T
EST
A
VAILABLE
A
PPLIED
V
ALUE
R
ELAY
I
NSTRUMENTS
D
ISPLAY
(±5%)
Winding 1 Line Currents
√
1.00 xI
n
(I
A
, I
B
, I
C
)
Winding 2 Line Currents
√
1.00 xI
n
(I
A
, I
B
, I
C
)
Winding 3 Line Currents
1.00 xI
n
(I
A
, I
B
, I
C
)
Winding 4 Line Currents
1.00 xI
n
(I
A
, I
B
, I
C
)
Winding 5 Line Currents
1.00 xI
n
(I
A
, I
B
, I
C
)
W1 EF/REF
0.200 xI
n
W2 EF/REF
0.200 xI
n
W3 EF/REF
0.200 xI
n
Voltage Input
1.00 xV
n
Table 4 - Measurement Accuracy
©2010 Siemens Protection Devices Limited