![Siemens 6SL3210-1PE21-1AL0 Manual Download Page 19](http://html.mh-extra.com/html/siemens/6sl3210-1pe21-1al0/6sl3210-1pe21-1al0_manual_377045019.webp)
Siemens PM240-2_EN_rev00-30082019.docx
3-11
Table 4 Technical data PM240-2, FSD (3 AC 380 V to 480 V ±10 %)
PM240-2 with integrated line filter
code
6SL3210-
1SE23-8AA0
1SE24-5AA0
1SE26-0AA0
1PE27-5AL0
Output current
Rated current In
Base-load current IH
Peak current Imax (3s over 300s)
Peak current Imax (57+3s over 300s)
A
A
A
A
38
32
64
48
45
38
76
57
60
45
90
67.5
75
60
120
90
Type rating¹)
on basis of In
on basis of IH
kW
kW
18
15
22
18.50
30
22
37
30
Rated pulse frequency
kHz
4
4
4
4
Power loss
kW
0.55
0.68
0.77
0.69
Cooling air requirement
m³/s
0.038
0.022
0.022
1.02
Sound pressure level LpA (1m)
dB
72
72
72
72
24 V DC supply
for the Control Unit
A
1.0
1.0
1.0
1.0
Rated input current²)
with integrated line reactor
A
36
42
57
70
Class J UL fuses
Rated current
A
50
70
90
100
NH fuses IEC 60947
Rated current
A
3NA3820
50
3NA3824
80
3NA3830
100
3NA3830
100
Circuit breaker type designation
IEC
60947
Rated current
A
3RV1042-
1JA10
45 … 63
3RV1042-
4KA10
57 … 75
3RV1042-
4KA10
57 … 75
3VL1712-
1DD33-0AA0
100 …125
Resistance value
ext. braking resistor
Ω
25
15
Max. cable length
to braking resistor
m
15
Line supply connection
L1, L2, L3
Tightening torque
Screw terminals
10.00
…35.00mm
2
(20 … 10 AWG)
2.5 … 4.5 Nm 22 lbf in
Motor connection
U2, V2, W2
Tightening torque
Screw terminals
10.00
…35.00mm
2
(20 … 10 AWG)
2.5 … 4.5 Nm 22 lbf in
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
2,50…16,0mm
2
(AWG20… AWG6)
Max. motor cable length ³)
shielded/unshielded
m
200/300
Degree of protection
IP20
Weight
with integrated line filter
kg
17.50
17.50
18.50
18.50
¹) Rated power of a typical standard induction motor at 400 V 3 AC
²) The input current depends on the motor load and line impedance. The input currents apply for a load with
the type rating (based on I
n)
for a line impedance corresponding to uk = 1%.
³) Max. motor cable length 200 m (shielded) for PM240-2 Power Modules with integrated line filter to
maintain the limit values of EN 61800-3 Category C2.
Summary of Contents for 6SL3210-1PE21-1AL0
Page 1: ...Siemens PM240 2_EN_rev00 30082019 docx 0 1 0 INVERTER SIEMENS S120 PM240 2 for HI POWER UNITS ...
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ...3 4 Siemens PM240 2_EN_rev00 30082019 docx Figure 3 PM240 2 frame size FSD FSE ...
Page 22: ......
Page 24: ......
Page 28: ......
Page 34: ......
Page 39: ...Siemens PM240 2_EN_rev00 30082019 docx 7 5 ...
Page 40: ......
Page 48: ......
Page 50: ......