Connecting-up
10.99
6SE7087-8NP87-0FB0
Siemens AG
5-2
Operating Instructions
SIMOVERT MASTERDRIVES
Output X2
Input X1
Fig. 5-1
Connection overview
♦
Use shielded control cables. The shield is to be connected at the
transmitter end and at the receiver end.
In the case of analog control cables, two-end shield connection can
lead to hum pick-up. In this case, the shield must only be connected
at one end, at the converter.
♦
Lay control cables and power cables separately. Power cables in
this context are the motor cable or connecting cables from the
converter’s DC link (terminals C/ L+ and D/ L-) to other components,
e.g. brake resistor. Control cables and power cables must never be
laid parallel to each other in a single cable pit, even if all the cables
are shielded.
Supply
Motor
MASTERDRIVES
Compact PLUS
EMC filter
Mounting plate
Su
p
p
ly
Lo
a
d
U2
V2
W2
PE2
U1
V1
W1
PE1
L1
L2
L3
PE
L1’
L2’
L3’
PE’
Fig. 5-2
Circuit diagram