![Siemens 6MD662 Manual Download Page 71](http://html.mh-extra.com/html/siemens/6md662/6md662_manual_377042071.webp)
Standard mapping 3-2
71
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
4.2.2
Measured values
•
Ref. to chap. 2.3.2 for notes regarding scaling of measured values.
4.2.3
Metered measurands
•
Ref. to chap. 2.3.3 for notes regarding routing and scaling of metered measurands.
4.2.4
Transformer tap position indications
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Transmission
as
14
3P1_V1 =
3P1 Phase to Earth Voltage V1
3276.7
Primary value
16
3P1_V2 =
3P1 Phase to Earth Voltage V2
3276.7
Primary value
18
3P1_V3 =
3P1 Phase to Earth Voltage V3
3276.7
Primary value
20
3P1_I1 =
3P1 Phase Current I1
3276.7
Primary value
22
3P1_I2 =
3P1 Phase Current I2
3276.7
Primary value
24
3P1_I3 =
3P1 Phase Current I3
3276.7
Primary value
26
3P1_P =
3P1 Active Power Three Phase
3276.7
Primary value
28
3P1_Q =
3P1 Reactive Power Three Phase
3276.7
Primary value
30
3P1_f =
3P1 Frequency
3276.7
Primary value
32
3P1_cosPhi =
3P1 Active Power Factor Three Phase
32.767
Primary value
34
3P1_V0 =
3P1 Zero Sequence Voltage
3276.7
Primary value
36
Td1 =
Transducer 1 (0...20 mA)
327.67
Secondary value
38
Td2 =
Transducer 2 (0...20 mA)
327.67
Secondary value
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(2
31
-1 corresponds to ...)
Internal
object no.
40
<user-defined>
not pre-allocated
2
31
-1 impulses
-
44
<user-defined>
not pre-allocated
2
31
-1 impulses
-
48
<user-defined>
not pre-allocated
2
31
-1 impulses
-
52
<user-defined>
not pre-allocated
2
31
-1 impulses
-
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
56
<user-defined>
not pre-allocated
-
57
<user-defined>
not pre-allocated
-
Summary of Contents for 6MD662
Page 6: ...Preview 6 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 8: ...Revision index 8 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 12: ...Table of contents 12 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 72: ...Standard mapping 3 2 72 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 86: ...Index 86 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...