![Siemens 6MD662 Manual Download Page 49](http://html.mh-extra.com/html/siemens/6md662/6md662_manual_377042049.webp)
Data of the PROFIBUS DP messages
49
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
Configuration data
PROFIBUS DP
master
At the configuration of a PROFIBUS DP slave of the SIPROTEC devices in the param-
eterization system of the PROFIBUS DP masters are to select the following modules
for the 6MD662/3/4 standard mappings and to allocate associated addresses in the
I/O addressing range of the PROFIBUS DP master:
Standard mapping 3-1:
Standard mapping 3-2:
Standard mapping 3-3:
Standard mapping 3-1:
1FH 1FH 1DH DFH 2DH
(78 bytes input-, 14 bytes output direction)
Standard mapping 3-2:
1FH 1FH 1FH 19H 29H
(58 bytes input-, 10 bytes output direction)
Standard mapping 3-3:
1FH 1FH 1DH DFH 2DH
(78 bytes input-, 14 bytes output direction)
Standard mapping 3-4:
1FH 1FH 1DH DFH 2DH
(78 bytes input-, 14 bytes output direction)
Module
Order number
Input address
Output address
0
Input - 16 Bytes
Adr_Ix
1
Input - 16 Bytes
16
2
Input - 14 Bytes
32
3
Input - 16 Words, consistent
46
4
Output - 14 Bytes
Adr_Ox
Module
Order number
Input address
Output address
0
Input - 16 Bytes
Adr_Ix
1
Input - 16 Bytes
16
2
Input - 16 Bytes
32
3
Input - 10 Bytes
48
4
Output - 10 Bytes
Adr_Ox
Module
Order number
Input address
Output address
0
Input - 16 Bytes
Adr_Ix
1
Input - 16 Bytes
16
2
Input - 14 Bytes
32
3
Input - 16 Words, consistent
46
4
Output - 14 Bytes
Adr_Ox
Summary of Contents for 6MD662
Page 6: ...Preview 6 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 8: ...Revision index 8 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 12: ...Table of contents 12 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 72: ...Standard mapping 3 2 72 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Page 86: ...Index 86 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...