Parameters/address space
4.2 Explanation of the parameters
IO-Link digital input/digital output module DIQ 16x24VDC/0,5A 8xM12 (6ES7143-5AH00-0BL0)
16
Equipment Manual, 08/2021, A5E47926885-AB
4.2
Explanation of the parameters
Diagnostics: Missing load voltage 2L+
Enabling of the diagnostics for missing or insufficient load voltage 2L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics, at short-circuit of an encoder supply or of an output to ground.
Freely assignable channel
With this parameter, you set whether the channel is to be operated as an input or output.
Reaction to CPU/master STOP
With this parameter, you set the reaction of the channels configured as output of the digital
input/output module after a CPU/master STOP:
•
Deactivate: The digital output is de-energized.
•
Keep last value: The last value of the digital output remains activated.
•
Output substitute value: The module outputs a configured substitute value.
Substitute value channel
With this parameter, you set substitute values for the digital outputs.