4 Commissioning
4.5 Automatic setting of control parameters
SIPART DR22 6DR2210
C79000-G7476-C154-03
223
Monitoring time
Direction
of the step
Amplitude
command
Start adaptation
Enter key (9)
Adaptation
after process
operation
Repeat
adaptation
Selection level
AdAP
Enter
key
(9)
Pre-adaptation
↗
Presettings
Adaptation LED (4) OFF
Exit
key
(2)
Old parameters
**.o are
overwritten by
new
parameters **.n
2)
see
fig.
3-3,
page
170
if nec. controller
selection
controller
I
or controller
II
,
Switch controller
to manual
operation, set the
desired operating
point and wait for
stationary
condition!
Filters tF
I
, tF
II
and tF1 to tFb
and floating time
tY must be set!
At S-controller
tA, tE and tY
must be set!
Enter
key (9)
1)
2)
Keys (13)
±∆
y
Process operation
level;
see
chapter 3.1, pg. 167
Switch controller
to automatic
operation, new
parameters **.n
are active
Old
parameters
**.o are
retained
cP.o
AH.o
cP.n
Pid.*
AH.n
Pi or Pid
Switch controller
to automatic
mode, old
parameters **.o
are active
During adaptation
Adaptation LED (4) flashing
Complete process display
cP.n
Pi.*
Exit
key
(2)
Parameterization mode AdAP
by error
messages
manual
of the adap-
via
tation
Exit key
procedure
see table 3-2, pg. 177
Error
message
display
tU oFF,0.1 to 24 h
dPv nEG, PoS
dY 0.5 to 90 %
**.o Pi or Pid
**.n Strt AdAP
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
Aborted adaptation
Adaptation LED (4) OFF
Post adaptation
Adaptation LED (4) ON
old
parameters
new
parameters
Figure 4-1
Parameterization mode AdAP
*
loop order 1 to 8
** Parameter name
1)
Enter function only active in manual operation (in the case of adaptation of the master controller in cascades (S1 = 5/6)
master controller set to Internal and Automatic)
2)
Error message
no AUto
If new parameters are selected and there is parameter control, the flashing error message no AUto appears after pressing
the Exit key (no automatic transfer).
Press the Enter key:
Error is acknowledged; return to parameterization mode AdAP; the parameters gained from
the adaptation can be noted.
Pressing the Exit key:
Jump to the parameterization preselection mode AdAP; the new parameters **.n are
deleted. On jumping to the parameterization mode AdAP, Strt AdAP appears in **.n.
Summary of Contents for 6DR2210
Page 2: ......
Page 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Page 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Page 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Page 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Page 269: ......