Wiring
3
3.1
Pin assignment of the I/O module RQ 4x120VDC-230VAC/5A CO
HA
[ID: 85663030923]
Terminal blocks
You can operate the I/O module with the following terminal blocks:
● 6DL1193-6TP00-0DK0, light
● 6DL1193-6TP00-0BK0, dark
The terminal block is not included in the scope of delivery of the I/O module and must be
ordered separately.
Note
You can find additional information on the configuration in the system manual.
WARNING
Risk of death or serious injury from electric shock!
Prior to working on the system and module, always disconnect them from the power supply.
NOTICE
External fuse for relay outputs
The outputs have to be protected with an external safety fuse with a maximum trip current of
6 A. The fuse has to be a micro fuse with the fast trigger characteristic.
Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)
Manual, 11/2017, A5E39389042-AC
11