Functions

Touch control TC5 (hereinafter refer to as TC5) is a KNX S-Mode multi-functional touch

panel for display, operation and control use. The device is equipped with a 5-inch color

capacitance touch screen with 480 × 854 resolutions.
The device is powered over KNX together with the DC 24...30 V auxiliary supply voltage.
It is operated directly via touch screen. Totally up to 15 function pages and 2 home pages

can be configured via ETS (ETS5.7 or later version).
Functionalities:

  Home page for navigation purpose

TC5 can set up multiple function pages for control and operation use. To easily navigate

to the desired function page, there are max. 2 home pages with up to 8 icons per page.

The navigation function can be enabled/disabled. If it is disabled, only one cover page is

available showing the date, time and temperature without home page.

  Multi-function page for lighting, blind, scene and value sending function

Lighting control includes switching and dimming. Blind function covers curtain type

open/close blind, roller shutter type up/down blinds and venetian blind with louver angles

adjustment. Scene operation such as scene recall via short press the scene icon and

storage via long press the scene icon is allowed. Upon demand, up to 120 channels are

available for each individual function.

  HVAC control covers several applications:

–  General temperature control applies for many room heating / cooling applications

such as FCU, chilled ceiling with 2-point or PI control. It can manage the room

temperature with setpoint (absolute or relative), heating / cooling selection, fan

operation (2 options: When fan operation is disabled, it is completely invisible; When

it is enabled, there are 5 types of fan speed: 3-speed, Off and Auto.), operation mode

changes (4 modes: Comfort, Standby, Economy and Protection).

–  VRF (Variable Refrigerant Flow) interface allows TC5 to act as the user interface to

operate VRF or VRV (Variable Refrigerant Volume) air conditioning devices with a

VRF gateway.

–  Enhanced floor heating control has dedicated timer and scene function. There is

indication of heating valve on/off and timer operation on screen.

–  Ventilation control has manual 3-speed fan switchover as well as auto control

(demand-based ventilation) via PM2.5 or CO

2

 value. It supports opening/closing of

heat recovery, filter life counting, alarm for filter change and filter life reset.

Up to 10 pages can be configured as HVAC control.

  Display air quality value from bus

This page can display various sensor readings such as temperature, relative humidity,

PM2.5, PM10, CO

2

, VOC, AQI, brightness and wind speed. Up to 4 parameters can be

displayed on one page and totally up to 10 pages can be configured as display page.

  Display energy metering value from bus

Up to 8 meters can be displayed on one page and totally up to 10 pages can be

configured as display page.

  Timer (schedule) function

Up to 16 schedules can be set. The schedule can be either daily or weekly and it is

configured via ETS.

  Event management

Up to 8 sets of event functions are available for setting. Up to 8 output telegrams can be

triggered by calling the scene number. Each output has 3 different data type options.

  Logic functions

There are up to 8 logic inputs configurable with logic capabilities of doing AND, OR, and

XOR, gate forwarding, threshold comparator and format conversion.

  RGB, RGBW control and color-temperature adjustment

TC5 can set up dimming control page for 4 types of color lights, which are 3-color RGB

light, 4-color RGBW light, 4-color RGBW light optional with color temperature adjustment

and brightness & color temperature adjustment.

  Display time, date, temperature, output day/night signal

  Proximity sensor, adjustment of screen brightness, buzzer

Summary of Contents for 5WG1205-2AB21

Page 1: ...ontroller and or ventilation Interface and operation for VRF devices VRF Variable Refrigerant Flow Display of temperature humidity air quality energy metering value etc Schedule event management and basic logic function Configurable navigation for up to 15 function pages Administrator function via password or bus objects Proximity sensor adjustment of screen brightness buzzer Customization possibl...

Page 2: ...ff and Auto operation mode changes 4 modes Comfort Standby Economy and Protection VRF Variable Refrigerant Flow interface allows TC5 to act as the user interface to operate VRF or VRV Variable Refrigerant Volume air conditioning devices with a VRF gateway Enhanced floor heating control has dedicated timer and scene function There is indication of heating valve on off and timer operation on screen ...

Page 3: ...No Product Description 1 Mounting plate For fitting onto a conduit box 1 2 Screws 2 Only for China market Note 1 Conduit box needs to be ordered separately 2 6 32 flat head machine screw is for US market Ordering When ordering specify product quantity product number stock number and name e g UP 205 21 5WG1205 2AB21 5 touch panel Product documentation Title Document ID Mounting instructions A6V1198...

Page 4: ...ensor Auxiliary power supply connection terminal Note Entering programming mode Click the setting icon in home page Goes to General Enable KNX programming then the colorful strip turns red and device can be configured via ETS KNX programming function need to be done by professional engineers Make sure this function is disabled during daily operation and if it is enabled The device can operate norm...

Page 5: ... device Wiring Equipped with protective features against over voltage over current short circuit and reverse polarity in the power supply All connectors must be soldered using tin wires Otherwise resistance will be generated in the contacts over time which cause unstable operation The device is powered with direct current Avoid reversing the positive and negative poles of the power supply When con...

Page 6: ... accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of ...

Page 7: ...ree of housing as per EN 60529 IP30 Environmental conditions Storage EN 60721 3 1 Class 1K3 Temperature 25 55 C Humidity 0 93 r h non condensing Transport EN 60721 3 2 Class 2K3 Temperature 25 70 C Humidity 0 93 r h non condensing Operation EN 60721 3 3 Class 3K5 Temperature 5 45 C Humidity 0 93 r h non condensing Mechanical conditions Storage EN 60721 3 1 Transport EN 60721 3 2 Operation EN 60721...

Page 8: ...tained based on human detection not an obstacle Built in temperature sensor Measuring accuracy at 25 C NTC 100k 1 K Display 5WG1205 2AB21 5 inch color capacitance touch screen 480 854 pixel Dimensions mm w h d 5WG1205 2AB21 86 148 8 32 5 Weight without with package 5WG1205 2AB21 192 376 g Materials and colors 5WG1205 2AB21 Rear housing PC V0 Front panel 6063 aluminum Touch panel Glass Film Film ...

Page 9: ...9 Siemens Datasheet A6V11980238_en _a Smart Infrastructure 2021 01 28 Diagrams Connection terminals DC DC Auxiliary power voltage DC 24 30 V KNX KNX KNX operating voltage DC 21 30 V ...

Page 10: ...to change without notice Document ID A6V11980238_en _a Edition 2021 01 28 Dimensions mm Support Hand over the operating instructions and all other technical product information to the client Return faulty devices with a return delivery note to the local Siemens office For technical questions contact 49 911 895 7222 49 911 895 7223 support automation siemens com http www siemens com supportrequest ...

Reviews: