background image

8/9 

 

LED display

 

 

LED 

Description 

Flashes a 1 second 
intervals  

The detector is in the start -up phase 
 

Flashes rapidly  

 

Error flashing, the detector has found an error  

Flickers for 20 s 
 

Teach-in via potentiometer is activated  

Lights up or flickers 
irregularly  

 

The detector is in walking test mode. 

 

Troubleshooting

 

 

Fault 

Cause  

Light does not switch 
on or off if presence 
is detected and in 
darkness 

Lux value is set too low; detector set to semi-
automatic; light was switched off manually via button; 
person not within detection area; obstruction(s) 
interrupting detection;  
time delay set too short 

Light stays on with 
detection 
 of presence despite 
sufficient brightness 

Lux value is set too high; light was briefly switched on 
manually via button detector is in test mode 

Light does not switch 
off, or light switches on 
spontaneously when 
no one is present 

Thermal sources of interference in the detection area: 
fan heaters, incandescent lamps/halogen spotlights, 
moving objects (e.g. curtains hanging in open 
windows); load (EBs, relays) not cleared 

Button does not work 

Device still in the start-up phase 

Device does not respond  Short circuit or several phases in parallel switching! 

Disconnect detector from the power supply for 5 min 
(thermal fuse) 

Error flashing 
(4 x per second) 

Error in self-test;  
device not functional! 

 

 

 

2

51

65

34

14

9_0

Summary of Contents for 5TC1585

Page 1: ...1 9 Bewegungsmelder 5TC1585 Movement detector 5TC1586 Detector de movimiento Détecteur de mouvement Betriebsanleitung Operating Instructions Manual de instrucciones Manuel d utilisation 2516534149_01 ...

Page 2: ...2 9 2516534149_01 ...

Page 3: ...TC1586 For Master Slave Switching Proper Use The detector controls the lighting It is designed for wall mounting in an interior switch range e g in a corridor staircase cellar toilet etc For use in normal ambient conditions Connection Use the same external conductor for all detectors Secure device with an upstream type B or type C circuit breaker EN 60898 1 with a maximum of 10 A L L Individual sw...

Page 4: ...he lighting The other detectors slaves 5TC1586 merely provide presence information A maximum of 6 detectors can be connected over a length of 50 m Installation For installation in device housing concealed housing size 1 Observe the recommended installation height of 0 8 m 1 2 m Ensure that there are no obstructions as infrared rays cannot pass through solid objects The detector is not suitable for...

Page 5: ...nd adapter frame should be ordered separately according to the following table Description and settings MLFBs Description 5TG6278 5TW00 Adapter frame and button titan white 5TG6278 5WH00 Adapter frame and button polar white 5TG6278 5AM00 Adapter frame and button aluminium metallic 5TG6278 5CM00 Adapter frame and button carbon metallic 5TG6278 5SW00 Adapter frame and button matt white 5TG6278 5SB00...

Page 6: ...ime 10 s 1 min 5 min 10 min 30 min If you wish to use the pulse function e g for a staircase light timer switch Set the potentiometer to As long as motion is detected the contact closes every 10 s for 0 5 s Test detection area walking test The walking test is used to test the detection area and to restrict it if necessary Set the time potentiometer TIME to test The detector always responds to move...

Page 7: ...ightness man semi automatic The lighting is always switched on manually It is switched off by the detector Manual operation using the button internal or external The button can be used to manually switch the lighting at any time Switching on manually When the button is pressed briefly the light switches on for a certain time depending on the duration of motion and the set time delay Switching off ...

Page 8: ...ction time delay set too short Light stays on with detection of presence despite sufficient brightness Lux value is set too high light was briefly switched on manually via button detector is in test mode Light does not switch off or light switches on spontaneously when no one is present Thermal sources of interference in the detection area fan heaters incandescent lamps halogen spotlights moving o...

Page 9: ... fluorescent lamps 1150 VA not with 5TC1586 LED lamps 2 W type 40 W 2 W type 450 W not with 5TC1586 Protection rating IP 20 in accordance with EN 60529 Operating temperature 15 C 45 C Brightness setting range 5 1000 lx not with 5TC1586 Lighting time delay 10 s pulse 30 min not with 5TC1586 Installation height 0 8 1 2 m Detection angle 170 Detection area across 14 x 17 m frontal 12 x10 m Dimensions...