Document No. 563-067 

Installation Instructions  

February 23, 2011 

Installation 

1.  Determine the optimal location of the RSX and 

antenna for RF communications. 

Ideally, the antenna should extend below the 
terminal box. 

2.  Mount the RSX using the provided screws. 

3.  Connect the RTS communication port of the 

TEC device to the RSX (Figure 4). The 
maximum cable length is 100 ft (30 m). 

NOTE: 

If you do not have the proper cable to 
connect the TEC device to the RSX in  
step 3, Table 1 on page 4 provides pin 
connections to make your own cable. 

4.  Connect to 24 Vac power (Figure 4). 

a.  Connect “H” and “N” on the RSX power 

connector to the TEC power source as 
shown. 

b.  Connect “E” on the RSX power connector 

to earth ground as shown.      

24 V-AC

C

E

H

C H

DO 1 DO 2 DO 3 DO 4 DO 5

NO C NO C NO C NO C NO C

DO 6 DI  3

DI  2

FLN

TRUNK

NO C AI  3

TX RX

+

-

S

BST

RTS

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

WLAN0090R1

TEC Power

(From Transformer)

TEC

(Typical)

Ground

24 Vac

Power Line

Alternate

Power

3M

TM 

 Scotchlok

TM

Power Connectors (Typical of 2)

1. Thread TEC power

wire through
connector.

2. Fold up flap to

lock TEC wire
into connector.

3. Insert power wire

from RSX into
connector so it
appears in window.

4. Use lineman’s

pliers to pinch
connecting bar in 
place and connect
wires internally.

5. Close connector

cover to secure
wires.

TEC

Power Wire

RSX

Power Wire

RSX/TEC

Connection

Cable

 

 

Figure 4.  RSX Communication and Power Wiring. 

 

Siemens Industry, Inc. 

Page 3 of 5

 

Summary of Contents for 563-069

Page 1: ...8 Remote Mount Antenna Transceivers do not come with antennas Antennas must be ordered separately Accessories 563 210 01 RSX TEC Connection Cable 3 ft 563 210 02 RSX TEC Connection Cable 12 ft 563 207 Auto binding cable to bind WRS RSX pair Warning Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Expected Installation Time 10 min...

Page 2: ...ng plenum with the entire antenna extending downwards below the VAV box Figure 2 Remote Mount Antenna The RSX is mounted inside the TEC or any metal enclosure and the antenna is brought through a 1 2 in 1 3 cm knockout Figure 3 The antenna extension cable is 12 in 30 cm long WLAN0088R1 VAV BOX VAV BOX VAV BOX Figure 2 RSX Mounted Outside Enclosure WLAN0089R1 Figure 3 RSX Mounted Inside Enclosure N...

Page 3: ...ce as shown b Connect E on the RSX power connector to earth ground as shown 24 V AC C E H C H DO 1 DO 2 DO 3 DO 4 DO 5 NO C NO C NO C NO C NO C DO 6 DI 3 DI 2 FLN TRUNK NO C AI 3 TX RX S BST RTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 WLAN0090R1 TEC Power From Transformer TEC Typical Ground 24 Vac Power Line Alternate Power 3MTM ScotchlokTM Power Connectors Ty...

Page 4: ...ed Page 4 of 5 Siemens Industry Inc c Connect the antenna wire securely to the RSX 6 Position the antenna in a vertical orientation up or down 7 Install and bind associated Wireless Room Sensor WRS to the RSX If the associated WRS is new or is shipped with the RSX install WRS per the Wireless Room Sensor WRS Installation Procedure 563 065 If the associated WRS is already installed bind the RSX and...

Page 5: ...nce will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equi...

Reviews: