Document No. 538-586
Installation Instructions
Rev. 3, November, 2001
Page 2 of 3
Siemens Building Technologies, Inc.
•
Individual fibers identified as Transmit and
Receive.
•
A report from the fiber installer showing the
loss of optic power per section of fiber cable,
including all connectors. The loss must be
less than the required link budget.
•
Source of transient protected for 115 Vac or
230 Vac. All field panel outlets are protected
or an MOV protected 120 Vac duplex outlet
(P/N 529-804), or three 250 V operation
(refer to Figure 7) can be ordered.
•
The BLN or FLN trunk has been checked for
opens, shorts, and proper shielding.
•
The mounting bracket (if used), or other
locally fabricated bracket, is available.
Instructions
1.
If wall or rack mounting brackets are being
used, refer to the installation instructions for the
brackets (P/N 538-718).
2.
Remove the protective cap from the transmit
port and transmit fiber, and connect the fiber to
the port labeled “TX” (refer to Figure 2). Do not
use any tools to tighten the connectors.
3.
Remove the protective cap from the receive
port and receive fiber, and connect the fiber to
the port labeled “RX” (refer to Figure 2). Do not
use any tools to tighten the connectors.
4.
Connect the BLN or FLN trunk to the trunk
connector. Then plug the connector into the
port labeled “Trunk” on the interface.
5.
Connect the earth ground wire (2’ green wire,
included) from the trunk shield connection to
earth ground. The ground can be either the field
panel chassis using the nutdriver to put the
ground terminal under the chassis mounting nut
or the electrical box which powers the interface.
6.
Connect the power connector into the interface
and plug the power pack into a transient
protected source.
The installation is now complete.
NT0214R1
BRACKET
FACE
BRACKET
INTERFACE
MOUNTING
SCREW
INTERFACE
BACK
END BEZEL
Figure 3. Rack Mount of Fiber Optic Interface (Side View).
FIBER OPTIC
TRUNK INTERFACE
Power
TX1
RX1
DUAL FIBER OPTIC
TRUNK INTERFACE
Power
TX1
RX1
TX2
RX2
FIBER OPTIC
TRUNK INTERFACE
Power
TX1
RX1
FIBER OPTIC
RS232 INTERFACE
Power
TX1
RX1
NT0212R2
RACK MOUNTING BRACKET
SPACER
SPACER
I
I
I
I
Figure 4. Multiple Unit Rack Mounting Installation.