Installation Instructions 

Document No. 538-586 

Rev. 3, December, 2001 

 

 
Fiber Optic Trunk Interface 

 

 

 

Page 1 of 3 

Product Description 

The Fiber Optic Trunk Interface (refer to Figure 1) 
converts the building level network (BLN) and floor 
level network (FLN) trunk electrical signals (RS-485) 
into light energy for transmission over a fiber optic 
cable and converts the light energy from a fiber 
cable back to RS-485 signals. The device is 
designed to work with either the BLN or FLN trunk at 
speeds of 300 bps to 230K bps, with a link budget of 
11.5 dB. 

There are no internal settings or user-serviceable 
parts in the Fiber Optic Trunk Interface. The 
interface requires a duplex fiber cable between 
interfaces (one fiber for transmit and one for 
receive). ST style port connectors are included. 

The Fiber Optic Trunk Interface is housed in a 1.5” × 
4” × 4” metal enclosure. It contains one power input 
receptacle, one three-position trunk port, one fiber 
transmit port, and one fiber receive port (refer to 
Figure 2). The interface is powered by a 6 Vdc 
external power pack (included). All circuits are 
supervised and power limited. 

Power

TX1

RX1

NT0281R1

FIBER OPTIC

TRUNK INTERFACE

s

 

Figure 1.  Fiber Optic Trunk Interface (Front View). 

538-735 Fiber to Trunk

TRUNK

S    -    + 

Operating Temp. 0-50 C (32-122 F)

PWR
6Vdc

150ma

NT0220R1

POWER INPUT

RECEPTACLE

TRUNK PORT 

RECEIVE 

PORT 

TRANSMIT

PORT 

TX1 RX1

 

Figure 2.  Fiber Optic Trunk Interface (Rear View). 

Product Numbers 

Description Product 

Number 

Fiber Optic Trunk Interface with ST 
port connectors 

538-735(115 Vac) 
538-735E (230 Vac) 

115 Vac 60Hz (14W) input 6 Vdc 
600mA output power pack for use 
with P/N 538-735 (included) 

538-757 

230 Vac 50 Hz (14W) input 6 Vdc 
1000 mA output power pack for 
use with P/N 538-745E (included) 

538-747 

 

 

 

CAUTION:   
Use only the plug-in transformer shipped 
with this device. 

120 Vac transient protected duplex 
outlet for 538-735 (not included) 

529-804 

Three 250V Metal Oxide Varistors 
(MOVs) included with P/N 538-
735E 

527-969 

Optional wall mounting kit (4”) 

538-708K 

Optional rack mounting kit (4”) 

538-716K 

 

Required Tools 

• 

Slotted screwdriver 

• 

19-inch rack position available if using the 
rack mounting kit 

• 

Wire cutters or wire strippers 

• 

7/16-inch (11.1mm) nutdriver 

Expected Installation Time 

15 minutes 

Prerequisites 

 

CAUTION:   

Avoid mounting the interface in a position 
that forces the fiber to make turns tighter 
than a three-inch radius. The mounting 
surface must also be vibration free. 

 

• 

Fiber cable installed and terminated with 
proper connector. 

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for 538-735

Page 1: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Page 2: ...runk Interface Front View 538 735 Fiber to Trunk TRUNK S Operating Temp 0 50 C 32 122 F PWR 6Vdc 150ma NT0220R1 POWER INPUT RECEPTACLE TRUNK PORT RECEIVE PORT TRANSMIT PORT TX1 RX1 Figure 2 Fiber Optic Trunk Interface Rear View Product Numbers Description Product Number Fiber Optic Trunk Interface with ST port connectors 538 735 115 Vac 538 735E 230 Vac 115 Vac 60Hz 14W input 6 Vdc 600mA output po...

Page 3: ... protective cap from the receive port and receive fiber and connect the fiber to the port labeled RX refer to Figure 2 Do not use any tools to tighten the connectors 4 Connect the BLN or FLN trunk to the trunk connector Then plug the connector into the port labeled Trunk on the interface 5 Connect the earth ground wire 2 green wire included from the trunk shield connection to earth ground The grou...

Page 4: ...rove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to technical editor sbt siemens com Document No 538 586 Printed in the U S A Page 3 of 3 NT0280R1 FIBER OPTIC TRUNK INTERFACE Power TX1 RX1 MOUNTING BRACKETS MOUNTING SCREWS VERTICAL SURFACE s Figure 5 Single Unit Wall Mounting Figure 6 Field Panel Mounting NT0226R1 AC HOT OUTLET BOX...

Page 5: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Reviews: