Installation Instructions

Hazardous voltage.
Will cause death or
severe injury.

Turn off and lock out all power
supplying this device before
removing cover(s) or device and
while cover(s) are removed.

Replace all covers and shields
before power supplying this
device is turned on.

Page 

3 of 4

Fig. 4

PUSH-TO-TRIP BUTTON

SEE FIGURES 5 and 6.

HANDLE

ON

TRIP

OFF

RESET

MANUAL OPERATION

Manual operation of the circuit breaker is controlled
by the circuit breaker handle and the PUSH-TO-
TRIP button.  The circuit breaker handle has three
indicating positions, two of which are molded into
the handle to indicate ON and OFF.  The third
position indicates a TRIP position and is between
the ON and OFF positions. (See Fig. 4)

A. Circuit Breaker Reset

After tripping, the circuit breaker is reset by
moving the circuit breaker handle to the reset
position and then moving the handle to the ON
position.

B. The PUSH-TO-TRIP Button

The PUSH-TO-TRIP button checks the tripping
function and is used to manually exercise the
operating mechanism.

Summary of Contents for 411625A00

Page 1: ... for use in individual enclosures panelboards switchboards or other approved equipment The installation procedure consists of inspecting attaching required accessories mounting the circuit breaker and connecting and torquing the line and load wire connectors Mounting hardware and unmounted wire connectors where required are available as separate catalog items A Turn off and lock out all power befo...

Page 2: ...lans refer to Fig 3 3 If device contains internal accessories make sure terminals can be connected when the circuit breaker is mounted Fig 3 Fig 2 9 75 4 40 6 86 OF HANDLE ESCUTCHEON OF HANDLE ESCUTCHEON DRILL AND TAP 1 4 20 HOLE 4 OR 6 PLS REQUIRED FOR SCJD6 SCLD6 ONLY OF HANDLE ESCUTCHEON SEE FIG 2 OF HANDLE ESCUTCHEON SEE FIG 2 1 50 3 00 1 25 2 50 3 07 1 50 2 00 3 25 6 50 4 Remove the line and ...

Page 3: ...Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP button The circuit breaker handle has three indicating positions two of which are molded into the handle to indicate ON and OFF The third position indicates a TRIP position and is between the ON and OFF positions See Fig 4 A Circuit Breaker Reset After tripping the circuit breaker is reset by m...

Page 4: ...tting lr is a percentage of the Maximum Continuous Current rating ln Two long time delay settings are available These are delay times of 3 seconds or 25 seconds at 6 times the Continuous Current Setting lr These are selected by using the appropriate area of the setting See Figure 5 Instantaneous Pickup All models have an Instantaneous Pickup adjustment This adjustment sets the Instantaneous Pickup...

Reviews: