3
Replacement of coil
Fig. 3: Contactor – Relay Connection
Table A:
Motor
Rating
At 415V
3ph 50Hz
Starter Type
Contactor
Relay 3UW51
Back-up Fuse
Rating
Cu
Cable
(mm
2
)
size
Max. Full Load Current (Amp)
HP
kW
Range
Code
##
HRC
type
3NA
7
Rewirable
3Ph, 415V,
4P
Squirrel
Cage IS
8789:1996
Table 4
3Ph, 415V,
2P Sub-
mersible
motor IS
9283:1995
Table 2
1Ph, 240V,
CSIR or
Split-
Phase IS
996-1979
Table 9
0.33 0.25
3TW72 91-1A* 64 3TS3010-0A##08KA0 0.63-1
0J
2A
36 SWG
1
-
-
3.8
0.75 0.55
3TW72 91-1A* 66 3TS3010-0A##08KA0 1-1.6
1A
6A
34 SWG
1
1.7
-
7
1
0.75
3TW72 91-1A* 68 3TS3010-0A##08KA0 1.6-2.5
1C
6A
27 SWG
1
2.2
-
7
1.5
1.1
3TW72 91-1A* 69 3TS3010-0A##08KA0 2-3.2
1D
10A
26 SWG
1
2.9
3.25
13
2
1.5
3TW72 91-1A* 71 3TS3010-0A##08KA0 3.2-5
1F
16A
25 SWG
1
3.8
4.5
18
3
2.2
3TW72 91-1A* 72 3TS3010-0A##08KA0 4-6.3
1G
16A
24 SWG
1.5
5.1
6.5
-
5
3.7
3TW72 91-1A* 74 3TS3010-0A##08KA0 6.3-10
1J
16A
21 SWG
1.5
8.1
10
-
7.5
5.5
3TW72 91-1A* 75 3TS3210-0A##08KA0 8-12.5
1K
25A
19 SWG
1.5
11.4
14.5
-
7.5
5.5
3TW72 91-1A* 77 3TS3210-0A##08KA0 10-16
2A
25A
18 SWG
2.5
-
-
-
10
7.5
3TW72 91-1A* 78 3TS3210-0A##08KA0 12.5-20
2B
32A
18 SWG
4
15.4
19.5
-
* Code for operating coil voltage, 50 Hz (B for 200-400V, W for 415V)
## Code for operating coil voltage, 50 Hz (Z6 for 200-400V, R0 for 415V)
Raja
+
Direct-on-line Starter
(For Single Phase connection)
Wiring Diagram for Single-Phase Motors
Note: Connect 3/L2 to 2/T1 by cable of suitable size. (Max. 4mm
2
)
S0 - OFF "O" (red) Button
S1 - ON "I" (green) Button
Q1 - Contactor
K1 - Bimetal Relay with
SPP feature
Hook on relay for
engagement
Contactor
outgoing terminals
Spare list
Sr.
No.
Description
Order No.
1
Contactor for 200-400V
3TS30-10-0AZ608K-A0
2
Contactor for 200-400V
3TS32-10-0AZ608K-A0
3
Contactor for 415V
3TS30-10-0AR008K-A0
4
Contactor for 415V
3TS32-10-0AR008K-A0
5
Relay
3UW51 02-##
6
Coil for 200-400V
3TY7 403-0AZ6
7
Coil for 415V
3TY7 403-0AR0
8
‘ON’ &’OFF’ Push Button
#
# – contact sales
Summary of Contents for 3TW7291-1A