Description
9229 0106 176 0-
21
2020-09-18
ops
operating cycles
Fig. 15
Mechanical data
Fig. 16
Rated data for latching and unlatching
AWG
American Wire Gauge
Fig. 17
Rated data for auxiliary switches
1-pole
3-pole
Mechanical data
3TM
12/13
14/15
32/33
34/35
36
Maximum mechanical switching frequency, without
latching and unlatching
ops/h
600
1 200
600
with latching and unlatching
ops/h
60
60
60
Mechanical service life, without latching and unlatching in an ambient temperature range
from -5 °C to +55 °C
ops
100 000
1 million
from +55 °C to +70 °C
ops
100 000
0.25 million
from -25 °C to -5 °C
ops
100 000
0.25 million
Mechanical service life with latching and unlatching
ops
100 000
200
000
Mass
kg
16
20 to 25
1-pole
3-pole
Latching and unlatching
3TM
12/13
14/15
32/33
34/35
36
Rated release voltage
U
a
(-
3
0
% to +10
%)
V
24 V DC to 32 V DC
V
48 V DC to 60 V DC
V
110 V DC to 125 V DC / 100 V AC to 120 V AC
V
220 V DC to 250 V DC / 230 V AC to 240 V AC
Power loss of the shunt release
(VA)
160
Required signal duration (for release signal)
ms
100 to 500
1-pole
3-pole
Auxiliary switch
3TM
12/13
14/15
32/33
34/35
36
Protection class on the front side
IP 20
Rated insulation level at pollution degree 3
V
500
Rated short-duration power frequency withstand
voltage
U
d
kV
6
Rated operating current
I
e
at rated voltage
U
r
Utilisation category AC 12 for alter-
nating current
AC 24 V
A
10
AC 230 V
A
10
Utilisation category AC 14 for alter-
nating current
AC 125 V
A
6
Utilisation category AC 15 for alter-
nating current
AC 24 V
A
6
AC 230 V
A
6
AC 400 V
A
3
Utilisation category DC 13 for direct
current
DC 24 V
A
6
DC 60 V
A
2
DC 110 V
A
1
DC 220 V
A
0.3
Terminal cross-sections of auxiliary switches as per IEC EN 60947-5-1
with flexible flex or wire end ferrule
mm
2
2 x (0.5 to 1.0), 2 x (0.75 to 2.5)
for AWG terminals
AWG
2 x (18 to 12)
Summary of Contents for 3TM
Page 12: ...Transport storage packaging 12 9229 0106 176 0 2020 09 18 Blank page ...
Page 26: ...Description 26 9229 0106 176 0 2020 09 18 Blank page ...
Page 36: ...Installation 36 9229 0106 176 0 2020 09 18 Blank page ...
Page 48: ...Maintenance 48 9229 0106 176 0 2020 09 18 Blank page ...
Page 50: ...Index 50 9229 0106 176 0 2020 09 18 Blank page ...