Wiring
4.1 Connections
3RW51 Soft Starter
54
Manual, 06/2019, A5E37108631002A/RS-AB/002
④
A1 / A2: Supply voltage for control terminals
⑤
Input IN to switch the drive on and off
⑥
Output 13, 14: To signal the operating state ON or RUN (parameterizable)
⑦
Output 23, 24: To signal the operating state BYPASSED
⑧
Output 95, 96 and 98: To signal faults
⑨
Analog outputs AQ-, AQ I+ und AQ U+: Connection of an evaluation unit to display the motor
current (optional)
•
AQ- / AQ U+: For evaluation units with output signal type Voltage, signal range 0 - 10 V
•
AQ- / AQ I+: For evaluation units with output signal type Current, signal range 4 - 20 mA
(factory setting)
Note
Parameterizing output 13 / 14
You will find more information on parameterization in Chapter Parameterizing output 13 / 14
(output signal ON or RUN) (Page 77).
Note
Parameterizing the analog output
You can parameterize the output of the analog output with the 3RW5 HMI High Feature
(Page 109).