3RK1703-2WB02-1CA1
17
System messages
The following messages must be acknowledged with the
key to return to the currently selected
function.
Message
Function
Significance
comerr
COM
Transmission error
dbladd
ADDR
Same address occurs twice (doublet)
Echo
Parameter
Received parameter XH
empty
Memory (copy)
Entire system has been copied
error
Data, Parameter
Address 0: Data and parameters cannot be read
found
ADDR
Slave addresses recognized
hiload
ASI V =
Current load too high for addressing device
lobatt
ASI V =
Battery can no longer supply full AS-i voltage
intern
ASI V =
No AS-i power pack on bus
master
ADDR, Profile, Data,
Parameter, Memory
Active master on bus
no asi
ADDR
Can’t find any slave addresses
no out
Data
This slave type has no outputs
no inp
Data
This slave type has no inputs
nopara
Para
Can’t find parameters
notequ
Memory (copy)
Can’t find suitable slave profile
ol.
ASI V=
Overload: U
AS-i
> 35 V
-pol
ASI V=
Voltage < -2 V (-pol blinks)
prgerr
ADDR, Profile, Data,
Parameter, Memory
Programming error
Prog
Data, Para, Memory (copy)
Transferring data to the slave
read
ADDR, Profile, Data,
Parameter, Memory
Reading data
search
ADDR, Data
Searching for slave addresses
ualbit
Data
Faulty valid bit
usenot
Data, Profile
Address 0 not allowed
useone
Memory (copy)
Only 1 slave can be copied, use addressing plug