background image

E87010-A0519-T003-A7-3RE4 

Page 2

Installation

General Maintenance

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092

A5E46948882A-002  

      Install in accordance with the National Electrical Code in       

      the United States, or Canadian Electrical Code in 

      Canada, and any applicable local codes.

1.   If the enclosure has a hinged door, the enclosure may be 

      fastened directly to a solid mounting surface via the four 

      mounting feet, which are included. All four mounting feet 

      must be attached to the enclosure using the supplied 

      hardware to retain the NEMA rating of the enclosure. 

      Follow the instructions included with the mounting feet.
      If the enclosure has a lift-off cover, the enclosure must be 

      fastened directly to a solid mounting surface via the 

      mounting holes in the back of the enclosure. 

      Mounting hardware is not included and any suitable 

      hardware may be used.
2.   If the NEMA Type 3/3R/4/12 enclosure is to be used as a 

      Type 3R enclosure, drill a 1/8" – 1/4" diameter drain hole 

      at the lowest point in the bottom of the enclosure.
3.   Turn off and lock out the power that will be supplying the 

      controller.
4.   Install conduit and necessary grounding means and wire 

      controller in accordance with the wiring diagram included 

      with the controller. Conduit knockouts are provided on the 

      enclosures with lift-off covers. For the hinged enclosures, 

      use UL Listed conduit hubs with the same NEMA Type 

      rating as the enclosure. Joint compound or equivalent is 

      recommended on conduit threads to prevent water from 

      entering the enclosure.
5.   Check that all wiring is secure and does not interfere with 

      proper operation of any device.
6.   Check that all wiring connections, including factory 

      connections are proper and tightened to the proper torque 

      values.
7.   Remove all foreign materials and debris from enclosure.
8.   For thermal OLRs, set the MANUAL / AUTO switch and 

      FLA dial as shown in Figure 3a. For solid-state OLRs, set 

      the Trip Class dial, MANUAL / AUTO switch and FLA dial 

      as shown in Figure 3b. For more information, refer to the 

      OLR instruction sheet. The publication number may be 

      found on the side of the device.
9.   Depress the OLR Reset button to make sure the OLR is 

      not tripped.
10. Close and fully latch the cover / door before applying 

      power. 
11. If a local selector switch is installed, make sure it is in the 

      OFF position.
12. Apply power and turn the controller on. The contactor 

      should energize. If it does not energize, troubleshoot the 

      controller to locate the issue.

Periodically conduct the following inspection and 

maintenance tasks. 

      

1.   Clean the inside of the enclosure by wiping off 

      dust and dirt which may have accumulated.
2.   Clean weep hole in bottom of NEMA Type 3R 

      enclosure to insure proper drainage.
3.   Check all screws for tightness.
4.   Refer to the OLR instruction sheet for 

      instructions on optional device tests.

Figure 1 

(Typical for both thermal and solid-state OLRs)

      

Reviews: