Siemens 3NJ-1-3B 01 Series Operating Instructions Manual Download Page 6

 3ZX1012-0NJ41-3AN1

 

 

Technische Daten (IEC/EN 60 947-3)

Technical data (IEC/EN 60947-3)

Elektrische Kenngrößen/Electrical characteristics

Nennspannung AC/rated voltage AC

U

e

V

400 ... 690, 3 ph. ±10%

max. Leistungsaufnahme/max. power consumption

P

v

VA

1,5

Bemessungsfrequenz/Rated frequency

-

Hz

50/60

Innenwiderstand/ Internal resistance

R

i

> 2

Ansprechschwelle/ Response threshold

U

o

V

> 5

Ausfall einzelner parallel geschalteter Sicherungen kann nicht erkannt werden!

No single defect detection of parallel connected fuses!

Relais/Relay

Auslösezeit/Response time

t

ms

> 500

Relaiskontakte/Relay contacts

-

-

1 x NC/1 x NO

Belastbarkeit AC/Current carrying capacity AC

-

-

AC 15: 24 V/4 A; 230 V/3 A

Belastbarkeit DC/Current carrying capacity DC

-

-

DC 13: 24 V/1 A; 220 V/0,5 A

Funktionsprinzip/Operational principle

-

-

Arbeitsstrom/Working current

EMV/EMC

IEC 61000-4-5

Stoßspannung/Surge 1,2/50ms

U

L-L

kV

6

IEC 61000-4-4

Schnelle transiente Störungen /Burst

U

L-L

kV

2

Allgemeine Daten/General data

Temperaturbereich/Temperature range

-

⁰C

-10 ... +55

Gebrauchsart/Utilization type

-

-

beliebig/as required

Schutzklasse/Protection class

-

-

IP20

Anzeige/Indication

Betrieb/Operation

-

-

1 LED (grün/green)

Störmeldung/Fault indication

-

-

3 LED (F1, F2, F3 rot/red)

Anschluss/Connection

Schraubklemmen/Screw terminals

starr/rigid

-

mm

2

0,14 - 2,5

flexibel/flexible

-

mm

2

0,14 - 1,5

Anzugsdrehmoment/Tightening torque

-

Nm

0,5 - 0,6

Montage/Mounting

-

-

Hutschiene (EN 50022)

Mounting rail (EN 50022)

Abmessungen B x H x T Dimensions W x H x D

-

mm

48 x 96 x 92

Gewicht /Weight

-

kg

0,2

Sicherungsüberwachung während des Hochspannungstests abtrennen!

Disconnect fuse monitoring while running the high voltage test!

All manuals and user guides at all-guides.com

all-guides

.com

Summary of Contents for 3NJ-1-3B 01 Series

Page 1: ...nsione pericolosa Può provocare morte o lesioni gravi Scollegare l alimentazione prima di eseguire interventi sull apparecchiatura Tensão perigosa Perigo de morte ou ferimentos graves Desligue a corrente antes de trabalhar no equipamento PRECAUCIÓN CAUTELA CUIDADO El funcionamiento seguro del aparato sólo está garantizado con componentes certificados Il funzionamento sicuro dell apparecchiatura è ...

Page 2: ...sition de la fourniture Alcance del suministro Configurazione di fornitura Escopo de fornecimento Teslimat hacmi Комппект поставки 发货内容 2 1 2 1 1 4mm 1 2 x 8 2 Nm PZ 2 1 2 x 6 5 2 Nm PH 2 2 Nm 2 5 mm2 FEP6YI1VDE0207 1 Ue 450 750 V TestvoltageUp 3000V All manuals and user guides at all guides com ...

Page 3: ...3ZX1012 0NJ41 3AN1 3 40 Nm AI Cu 25 300 mm2 32 Nm M10 30 35 Nm M12 35 40 Nm M12 35 40 Nm 4 3 m m 1 2 3NJ4911 3BA01 3NJ4918 1AA00 35 Nm 5 10 mm 35mm 1 2 All manuals and user guides at all guides com ...

Page 4: ...perating state Busy F1 F2 F3 NO contact 13 14 NC contact 21 22 no line voltage off off off off open closed fuse 1 3 o k Phase 1 3 o k on off off off open closed fuse 2 defect Phase 1 3 o k on off on off closed open LEDverte LED rouge LED rouge LED rouge Relais État de fonctionnement appareil actif F1 F2 F3 NO 13 14 NF 21 22 pas de tension en ligne éteinte éteinte éteinte éteinte ouvert fermé Fusib...

Page 5: ...do Fusível 1 3 o k fase 1 3 o k aceso apagado apagado apagado aberto fechado Fusível2defeituoso fase1 3o k aceso apagado aceso apagado fechado aberto LEDyeşil LED kırmızı LED kırmızı LED kırmızı Röle İşletim durumu Busy F1 F2 F3 Kapayıcı 13 14 Açιcι 21 22 Şebeke gerilimi yok Kapalı Kapalı Kapalı Kapalı Açιk Kapalι Si 1 3 o k Faz 1 3 o k Açιk Kapalı Kapalı Kapalı Açιk Kapalι Si 2 bozuk Faz 1 3 o k ...

Page 6: ...A Funktionsprinzip Operational principle Arbeitsstrom Working current EMV EMC IEC 61000 4 5 Stoßspannung Surge 1 2 50ms UL L kV 6 IEC 61000 4 4 Schnelle transiente Störungen Burst UL L kV 2 Allgemeine Daten General data Temperaturbereich Temperature range C 10 55 Gebrauchsart Utilization type beliebig as required Schutzklasse Protection class IP20 Anzeige Indication Betrieb Operation 1 LED grün gr...

Page 7: ...3ZX1012 0NJ41 3AN1 7 All manuals and user guides at all guides com ...

Page 8: ...ZX1012 0NJ41 3AN1 Subject to change without prior notice Store for use at a later date Printed in the Federal Republic of Germany Siemens AG 2006 Abmessungen Dimensioni Dimensions Dimensões Dimensions Ebatlar Dimensiones Габаритнтные размеры 尺寸 All manuals and user guides at all guides com ...

Reviews: