![Siemens 3AK Operating Instructions Manual Download Page 39](http://html.mh-extra.com/html/siemens/3ak/3ak_operating-instructions-manual_376949039.webp)
Mounting
9229 9923 176 0B
39
2013-09-09
Removing the transport securing device from the undervoltage release
Undervoltage release (Y7)
present?
The vacuum circuit-breaker modules with an undervoltage release (Y7) 3AX1103
are supplied with a transport securing device.
•
Remove the two top screws (60.2) from the cover (60.1).
•
Undo the two bottom screws (60.2) on the cover (60.1) until the cover (60.1) can
be taken off.
•
Slightly tilt the cover (60.1) of the mechanism box and lift off.
•
Shift the locking screw of the striker from position A to B (see reference note in
mechanism box [60.] of the vacuum circuit-breaker module).
•
Replace the cover (60.1) in the reverse order
•
and fasten the screws (60.2) with a tightening torque of 10 Nm.
Fig. 47
Removing the cover
Fig. 48
Removing the transport securing device
A
B