![Siemens 3AK Operating Instructions Manual Download Page 20](http://html.mh-extra.com/html/siemens/3ak/3ak_operating-instructions-manual_376949020.webp)
Description
20
9229 9923 176 0B
2013-09-09
Auxiliary switch S1
Breaking capacity
Fig. 17
Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for
delivery: with 6 or 12 NO/NC contacts each.
Rated insulation voltage:
250 V AC/DC
Insulation group:
C as per VDE 0110
Continuous current:
10 A
Closing capacity:
50 A
Fig. 16
Auxiliary switch (68.)
AC 40 to 60 Hz
DC
Operating voltage
Operating current
Operating voltage
Operating current
U (V)
I (A)
U (V)
I (A)
Ohmic load
Inductive load
(T = 20 ms)
Up to 230
10
24
10
10
48
10
9
60
9
7
110
5
4
220
2.5
2