First closing operation
If all functions have been checked and are ok, switch on high-voltage while
observing all of the safety regulations and operative requirements.
Charging the closing spring
If the supply voltage is applied, the closing spring (62.) is automatically charged by
the motor (50.4).
Hand crank
If the supply voltage fails, the closing spring (62.) can be charged with a hand crank
(50.).
1. For this, fit the hand crank (50.) onto the hand crank coupling (50.5) through the
opening (50.1) with the adapter pushed forward (50.6).
2. Turn clockwise until the spring state indicator (55.) changes over:
WARNING
Do not commission the vacuum circuit-breaker if there are malfunctions.
If the malfunctions or the damage cannot be remedied, contact a Siemens
representative or Siemens Service and, if necessary, send back the vacuum
circuit-breaker.
WARNING
Risk of injury if hand cranks other than the original hand crank are used.
When the supply voltage is present, the motor immediately recharges the spring
after a closing operation. If the hand crank does not have a slip coupling, the hand
crank will also rotate.
To avoid injuries caused by the motor starting suddenly, the vacuum circuit-
breaker must be charged only using the original hand crank.
Relaxed
Charged
Fig. 63
Charging the closing spring with the hand
crank
Fig. 64
Operating elements and spring state indicator