Description
9229 9992 176 0D
35
2013-07-08
Per phase one vacuum circuit-breaker
Fig. 46
Technical data - connection of one vacuum circuit-breaker per phase
Dimensions and weights
The dimensions of the vacuum circuit-breaker can be taken from the relevant
dimension drawing. If required, these are available from your Siemens
representative.
The weight is given on the rating plate of the vacuum circuit-breaker (see Fig. 44) or
can be taken from the relevant dimension drawing.
Note
If one vacuum circuit-breaker is ordered per phase, the three vacuum circuit-
breakers are synchronised at the factory. If one of the vacuum circuit-breakers is
exchanged, the three vacuum circuit-breakers must be re-synchronised.
Rated voltage*
U
r
kV
12**
17,5
24
Rated operating current
I
r
A
4000
4000, 5000,
6300, 8000,
10000, 12000
4000, 5000,
6300, 8000,
10000, 12000
Rated lightning impulse withstand voltage (peak value)
U
p
kV
75
110
125
Rated power frequency withstand voltage (effective value)
U
d
kV
28
50 50
Rated short-circuit breaking current
I
sc
kA
90
50, 63, 72, 80
50, 63, 72
Distance between pole centres
mm
**
275
300
Rated operating sequence
A, B
A, B
A, B
A
O - 3 min - CO - 3 min - CO; operating sequence with and without load
B
CO - 30 min - CO; operating sequence in the event of short-circuit current
*
In the event of a rated frequency
f
r of 50/60 Hz
**
Vacuum circuit-breaker with one pole assembly
**
Summary of Contents for 3AH37
Page 4: ...4 9229 9992 176 0D 2013 07 08 Blank page ...
Page 50: ...Installation 50 9229 9992 176 0D 2013 07 08 Blank page ...
Page 54: ...Operation 54 9229 9992 176 0D 2013 07 08 Blank page ...
Page 60: ...Maintenance 60 9229 9992 176 0D 2013 07 08 Blank page ...
Page 62: ...Index of keywords 62 9229 9992 176 0D 2013 07 08 Blank page ...