Auxiliary switch S1
Breaking capacity
Fig. 33
Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for
delivery: with 6 or 12 NO / NC contacts each.
Rated insulation voltage:
250 V AC/DC
Insulation group:
C as per VDE 0110
Continuous current:
10 A
Closing capacity:
50 A
Fig. 32
Auxiliary switch (68.)
AC 40 to 60 Hz
DC
Operating voltage
Operating current
Operating voltage
Operating current
U (V)
I (A)
U (V)
I (A)
Ohmic
load
Inductive load
(T = 20 ms)
Up to 230
10
24
10
10
48
10
9
60
9
7
110
5
4
220
2,5
2