49
Problem
Symptoms
Possible causes and remedies
Circuit breaker fails to close.
No sound of circuit breaker closing.
CLOSE/OPEN indicator (58.0) in
OPEN position.
1. Manual opening lever is in the lockout position (114.0). S6 is open.
2. Control voltage is absent. Check the:
Control power disconnect device in the relay and control compartment
Supply of control power - check incoming control voltage
Controller board
LEDs (105.1) should show green.
Pay attention to damage to wiring, terminals and connectors.
3. Internal position switch OPEN (113.2 S5) is not in OPEN position.
4. Capacitors are not charged sufficiently. Check the:
Connector (105.2) from capacitors to controller board (105.0)
correctly and firmly connected
Connector on the capacitor board for tight seat
Capacitor board.
Pay attention to damage to wires and signs of capacitor damage.
5. Check the linkage assembly including the opening spring.
6. Interruption of the circuit of magnetic-actuator's coil (101.0).
7. If the red LED is illuminated, check these possible causes:
Actuator position inconsistent, S4 or S5 malfunction or connections to
controller board incorrect
Lockout switch S6 activated or not connected correctly
Coil circuit connections damaged or incorrect
Capacitor board(s) damaged, or connections incorrect.
8. If the yellow LED is illuminated (temporarily), additional time is
necessary for capacitors to reach sufficient charge.
9. If the yellow LED is illuminated (continuously), the capacitor board(s) is
damaged or not connected properly.
10. If no LEDs are illuminated, refer to item 7.
11. If the green LED is illuminated, the controller self-test process was
successful. Refer to item 5.
Circuit breaker fails to trip.
No sound of circuit breaker closing.
CLOSE/OPEN indicator (58.0) in
CLOSED position.
1. Control voltage is absent. Check the:
Control power disconnect device in the relay and control compartment
Supply of control power - check incoming control voltage
Controller board
LEDs (105.1) should show green.
Pay attention to damage to wiring, terminals and connectors.
2. Internal position switch CLOSED (113.1, S4) is not in CLOSED position.
3. Capacitors are not charged sufficiently. Check the:
Connector (105.2) from capacitors to controller board (105.0)
correctly and firmly connected
Connector on the capacitor board for tight seat
Capacitor board.
Pay attention to damage to wiring and signs of capacitor damage.
4. Check the linkage assembly including the opening spring.
5. Interruption of the circuit of magnetic-actuator's coil (101.0).
Table 8: Vacuum interrupter stroke
Table 9: Troubleshooting