ANCB LEDs Description and Operations,
Continued
Figure 4-2 shows the edge visible LEDs on the ANCB. The LED labels
are silk-screened adjacent to each LED on the ANCB.
Figure 4-2: ANCB/DN LED
Indicators
CL
Use the following Table 4-1 to determine the error condition. FAULT
errors can only be cleared with a board reset.
Table 4-1: Error Codes
NUMBER
of Blinks
Type of Error
Corrective Action
1
RAM FAILURE
Replace Board
2
FLASH FAILURE
Reload Firmware or
Replace Board
3
ETHERNET FAILURE
Replace Board
4
DataNET FAILURE
Replace Board
6
DUPLICATE IP
Change Board IP address
8
WRONG LOOP
Change Loop Number
9
WRONG JUMPER
CONFIGURATION
Check J10 and J11
Connections
10
DUPLICATE UNIT NUMBER
Change Unit Number
50
•
Troubleshooting
2000592-001