● If you are using cable glands, use only certified cable glands with strain relief. Comply with
the installation and operation conditions specified in the certificate for these cable glands
and check that they have been complied with.
● Correctly close unused threads or holes, maintaining the IP degree of protection. The IP
degree of protection is stamped on the rating plate.
● Replace any unused cable glands by certified screw plugs.
6.4.2
Bringing cables into the terminal box 1XB.. and routing them with onion sealing ring
The following terminal boxes may be equipped with an onion sealing ring.
Table 6-5
Terminal boxes with onion sealing ring
Terminal box
Onion sealing ring
1XB9600
Standard design
1XB1621, 1XB1631, 1XB1634
Optional
The connecting cable is sealed at the cable entry location using a cut-out sealing insert and
is fastened using a strain relief device.
Bringing cables into the terminal box and connecting them
The terminal box is opened, the cable cut to the correct length and stripped back. Make sure
that no external forces are acting on the cable connection.
1P
ཱ
ི
Figure 6-4
Strain relief device and sealing insert
1. Remove the top part of the strain relief
③
and release the fixing screws for the bottom part
of the strain relief
②
. The strain relief device can be located either in the terminal box or
externally. If necessary, switch the direction sense of the strain relief device.
2. Cut the seal insert
①
so that its opening is 1 to 3 mm smaller than the diameter of the cable.
3. Pull the sealing insert over the end of the cable.
Electrical connection
6.4 Connection
SIMOTICS TN Series N-compact 1LA8
70
Operating Instructions 05/2014