IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22
Pag. 81 di 258 + FR
P
RELIMINARY OPERATIONS AND FIRST START
-
UP
Visual check of the connection
Make sure that all the connections have been made by following carefully the instructions given in the "Connections"
paragraph.
Check that all the isolators are open.
Closure of the battery fuse holders
Close the 4 battery fuse holders (SWBATT) as shown in the figure below.
WARNING: if an external Battery Box is present and the connection does not comply with the instructions
given in "Connecting the UPS to the Battery Box (optional)" paragraph, the battery fuses and other
protections may result damaged. In that case, please contact the Customer Service department, in order to
prevent further damages to the UPS.
When the fuses are closed, a small arc may occur due to charge of the condensers inside the UPS. This is
normal, and does not cause faults and/or damages.
UPS powering
Close the protections upstream the UPS.
Closure of the input and output isolators
Close the SWIN and SWBYP (if present) input isolators. Close the SWOUT output isolator but leave the SWMB
maintenance isolator open.
Summary of Contents for Safepower-Evo-HF 30
Page 2: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 2 di 258 FR...
Page 35: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 35 di 258 FR MENU DISPLAY...
Page 86: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 86 di 258 FR MENU DISPLAY...
Page 137: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 137 di 258 FR DISPLAY MEN...
Page 188: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 188 di 258 FR MENU AFFICHEUR...
Page 239: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 239 di 258 FR MEN PANTALLA...
Page 258: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 258 di 258 FR...