![SICK PBT Operating Instructions Manual Download Page 26](http://html1.mh-extra.com/html/sick/pbt/pbt_operating-instructions-manual_1264714026.webp)
Operating Instructions
PBT
26
© SICK AG • Germany • All rights reserved
8013153/V620/2012/03/12
Specifications
Model PBT
Signal output and
R
A
in Ohm
4 ... 20 mA, 2-wire
R
A
≤
(L
+
– 8 V) / 0.02 A
maximum ohmic load R
A
0 ... 10 V, 3-wire
R
A
> 10 k
0 ... 5 V, 3-wire
R
A
> 5 k
{Other signal output on request}
Response time
ms
< 4
Current consumption
mA
Signal current (max. 25) for current output
Max. 8 for voltage output signal
Insulation voltage
VDC
500
2)
2)
The power supply for the pressure transmitter must be made via an
energy-limited electrical circuit per section 9.3 of UL / EN / IEC 61010-1,
or an LPS to UL / EN / IEC 60950-1, or Class 2 per UL1310/UL1585 (NEC
or CEC). The power supply must be suitable for operation above 2,000 m
should the pressure transmitter be used at this altitude.
Non-linearity
% of span
≤
± 0.25 optional
(BFSL) according to IEC 61298-2
≤
± 0.5
(BFSL) according to IEC 61298-2
Adjusted in vertical mounting position with lower pressure connection.
Accuracy
3)
% of span
≤
± 0.5
(with non-linearity 0.25 %)
≤
± 0.6
(with non-linearity 0.25 % and with signal output 0 ... 5 V)
≤
± 1.0
(with non-linearity 0.5 %)
3)
Including non-linearity, hysteresis, zero point and full scale error (corresponds to
error of measurement per IEC 61298-2).
Zero offset
% of span
≤
0.15 typ.,
≤
0.4 max.,
(with non-linearity 0.25 %)
≤
0.5 typ.,
≤
0.8 max.,
(with non-linearity 0.5 %)
Hysteresis
% of span
≤
0.16
Non-repeatability
% of span
≤
0.1
Long-term drift
% of span
≤
0.1
according to IEC 61298-2
Signal noise
% of span
≤
0.3
GB
8. Specifications