t
S
•
Setting “30 ms”: t
S
= 30 ms
•
Setting “40 ms”: t
S
= 40 ms
•
Setting “50 ms”: t
S
= 50 ms
The test pulses of the other OSSD pairs are each offset by t
S
.
OSSD 1.A
V
t
OSSD 1.B
V
t
≤ 300 µs
≤ 300 µs
S
4 × t
Figure 96: Duration and time offset for the switch-off tests in an OSSD pair
t
S
•
Setting “30 ms”: t
S
= 30 ms
•
Setting “40 ms”: t
S
= 40 ms
•
Setting “50 ms”: t
S
= 50 ms
13.6
Sensing range
The effective protective field range depends on the variant, on the set scan cycle time
and on the set object resolution.
Table 39: Protective field range (devices with a max. protective field range of 4.0 m)
Scan cycle time 30 ms
≥ 70 mm
4.00 m
4.00 m
50 mm
3.50 m
3.00 m
40 mm
3.00 m
2.30 m
30 mm
2.30 m
1.70 m
Table 40: Protective field range (devices with a max. protective field range of 5.5 m)
Scan cycle time 30 ms
≥ 70 mm
5.50 m
4.00 m
50 mm
3.50 m
3.00 m
40 mm
3.00 m
2.30 m
30 mm
2.30 m
1.70 m
Table 41: Protective field range (devices with a max. protective field range of 9.0 m)
50 ms scan cycle time
≥ 150 mm
9.00 m
9.00 m
70 mm
9.00 m
7.00 m
60 mm
8.00 m
6.00 m
50 mm
7.00 m
5.00 m
40 mm
5.00 m
4.00 m
TECHNICAL DATA
13
8025424/1ELL/2022-01-21 | SICK
O P E R A T I N G I N S T R U C T I O N S | microScan3 Pro I/O
189