Technical Information
Chapter
2
HC8X Heat Control
Installation/Removal
8010043
©
SICK AG · All rights reserved
2-19
2
Installation/Removal
2.1
Selecting the Installation Location
Short-circuit caused by moisture or dust!
Observe the degree of protection (IP 20) when selecting the installation location.
Do not install the control unit in a humid or dusty environment.
Distance between HC8X and Measuring System PC
The length of the optical fiber between the HC8X or an I/O module box and the measuring
system PC may not exceed 60 m.
2.2
Installing the HC8X
Control unit damage by overheating!
Install the HC8X horizontally, if possible.
If required, install the HC8X vertically so that the ventilator on the side points downward
Ensure adequate heat dissipation.
Install the HC8X so that the internal control unit ventilator can draw in cool air unhin-
dered.
1.
Position the HC8X on the installation plate or a control unit carrier; observe a minimum
distance of 5 cm between the heat sink and adjacent control units.
2.
Ensure a firm base and good attachment of the control unit.
564
71
109
Ventilator
Heat sink
Fig. 2-1:
HC8X Attachment