Technical specifications
8.1.3
PROFIBUS DP
Interface
Minimum
Typical
Maximum
Fieldbus PROFIBUS
DP-V0
Interface level
RS-485
Connector technology
D-Sub socket 9-pin
Slave address (set via
rotary switches)
0
99
Slave address (set via
Flexi Soft Designer)
3
125
Baud rate
(automatic adjustment)
12 MBaud
Baud rate (kbit/s
with standard cable)
Max. cable length
9.6/19.2/93.75
1200
m
187.5
1000
m
500
400
m
1 500
200
m
12 000
100
m
Cable parameters see section 6.1 “PROFIBUS DP gateway” from page 116.
8.1.4
CANopen
Interface
Minimum
Typical
Maximum
Fieldbus CANopen
DS-301
Interface level
RS-485
Connector technology
5 pin open style connector
Slave address (set via
rotary switches)
0
99
Slave address (set via
Flexi Soft Designer)
1
127
Baud rate (kbit/s
with standard cable)
Max. cable length
125
500
m
250
250
m
500
100
m
800
40
m
1 000
20
m
Cable parameters see chapter 6.2 “CANopen gateway” from page 130.
18)
In order to set the slave address via software, the hardware setting for the address must be “00”.
19)
In order to set the slave address via software, the hardware setting for the address must be “00”.
Tab. 152: Technical
specifications FX0-GPRO
Tab. 153: Technical
specifications FX0-GCAN