At altitudes up to 2,000 m
above sea level … 3,000 m
above sea level
–25 °C … +50 °C
At altitudes 3,000 m above sea
level … 4,000 m above sea level
–25 °C … +45 °C
Storage temperature
–25 °C … +70 °C
Air humidity
10% … 95%, non-condensing
Operating altitude
Max. 4,000 m above sea level
Mechanical strength
Vibration resistance
5 Hz … 200 Hz / 1 g (EN 60068-2-6)
Shock resistance, single shock
15 g, 11 ms (EN 60068-2-27)
Operating data
Protection class
III (EN 61140)
Immunity to interference
EN 61000-6-2
Emitted interference
EN 61000-6-4
Connections
Connection type
Spring terminals
RJ45 female connectors
Wire cross-section
Single wire or fine-stranded wire: 0.14 mm² … 1.5 mm²
Fine-stranded wire with ferrule:
a) with plastic ferrule max. 1.0 mm²
b) without plastic ferrule max. 1.0 mm²
AWG according to UL/CSA: 26 … 14
For UL and CSA applications:
Use copper conductors only min. rated for 85°C.
Housing
Enclosure rating
IP20 (EN 60529)
Contamination rating
2 (IEC 61010-1)
Control device type
Open device (IEC 61010-2-201)
Weight (± 5%)
111 g
Voltage supply (A1 / A2)
Table 16: Voltage supply
Supply voltage U
B
+24 V DC
Tolerance of supply voltage
–30% / +25% (16.8 V … 30 V)
Type of supply voltage
PELV or SELV
The supply current must be limited externally to max. 4 A
– either by the voltage supply unit used, or by means of
a fuse.
Max. power loss
4.9 W
Power consumption at nominal volt‐
age
(without outputs)
2.4 W
Short-circuit protection
1)
Max. 4 A/Min. 30 V
Safety fuse with triggering characteristic: slow-blow
UL/CSA applications: UL-listed fuse according to
UL 248-14 required
Overvoltage category
II (EN 61131-2)
12
TECHNICAL DATA
34
O P E R A T I N G I N S T R U C T I O N S | Flexi IO XTDO1
8024583/2020-11-10 | SICK
Subject to change without notice