Chapter
5
Operating Instructions
CLV 45x Bar Code Scanner
5-4
©
SICK AG · Division Auto Ident · Germany · All rights reserved
8 009 139/K949/06-06-2002
Electrical installation
5.5
Carrying out the electrical installation
5.5.1
Overview of the connection steps
•
Connecting the supply voltage
•
Wiring the host interface
•
Connecting the PC (wiring the terminal interface)
•
Wiring the "Sensor 1" and "Sensor 2" switching inputs
•
Wiring the "Result 1" and "Result 2" switching outputs
5.5.2
Aids
•
Tool
•
Digital measuring device (current/voltage measurement)
5.5.3
Connecting the supply voltage
If the CLV is supplied with power via the AMV/S 40 connection module, the supply voltage
does not have to be wired separately.
1.
Ensure that the supply voltage of the AMV/S 40 is switched off.
2.
Connect the 15-pin cable plug of the CLV to the corresponding socket of the AMV/S 40
and screw it tight. The connection cable can be extended by 2 m by using the extension
cable No. 6 010 075.
The data and function interfaces of the CLV are contacted to the connection module.
– or –
In case of power supply via a non-SICK supply system device:
¾
Connect the power supply to the red wire (Pin 1, +10 ... +30 V DC) and the black wire
(Pin 5, GND) of the Cable No. 6 010 137 (also refer to
Pin
Signal
Wire color
1
+10 ... +30 V DC
Red
2
RxD (terminal)
Violet
3
TxD (terminal)
Yellow
4
Sensor 2
Red-black
5
GND
Black
6
RD+ (RS-422/485)
Light blue
7
RD– (RS-422/485); RxD (RS-232)
Blue
8
TD+ (RS-422/485)
Turquoise
9
TD– (RS-422/485); TxD (RS-232)
Green
10
CAN H
Gray
11
CAN L
Pink
12
Result 1
Brown
13
Result 2
Orange
14
Sensor 1
White
15
SensGND
White-black
–
Shield
White-green
Table 5-5: Wire color assignment of cable No. 6 010 137 (open end)