Use the Siemens TCON function block
To establish an open TCP connection, the following communication blocks are available
in the Siemens standard library (see
■
TCON
for establishing the connection
■
TDISCON
for terminating the connection
■
T_CONFIG
for configuring the interface
Figure 21: Siemens standard library
In this example, the
TCON
function block (see
) is called in OB1 with the
instance data block
TCON_DB
. In the case of a reboot, the “
#Initial_Call
” flag triggers
the the
TCON
function block to open the TCP communication. The
ID
parameter of the
TriSpector1000 function block input must have the same value as the
ID
input of the
TCON
function block (will be set up in next step).
Figure 22: Establish TCP connection
The connection parameters for setting up the TCP connection are stored in an automat‐
ically generated data block. Open the
Properties
tab for the
TCON
function block to make
the settings and generate the data block, see
ANNEX
12
8022395/19OK/2020-12 | SICK
O P E R A T I N G I N S T R U C T I O N S | TriSpectorP1000
51