18 GC250 Technical Manual
EAAM057608EN
Engine instruments analogue
inputs
Three inputs for resistive sensors plus one input for measuring and
compensation of the reference potential of their common minus.
Resistance measuring range:
range: 0...1kohm with error < 1%
extended: 0
– 0...3kohm with error < 2%
The three measurement inputs can also be used as digital inputs with
GND activation, with status change voltage if 1.17VDC
Voltage compensation range of the reference point, with
Rsensors=100ohm:
-2.7...+3.5VDC
Analogue inputs
The input T.16 can be configured from parameter to obtain voltage
signals 0..10VDC referred to GND (T.01)
CANBUS Connection
USB 2.0 for non permanent connection to PC (max 6m) only for the
configuration of parameters with program SICES BoardPrg3.
The device is directly supplied by PC and turns on in OFF/RESET
mode when it is connected, with maximum consumption of 250mA
from USB port.
CANBUS Connection
CanBus connection without galvanic isolation with protocol SAEJ1939
and MTU for the connection to ECU engine control. Fix internal
termination of 120ohm
Display
Graphic transflective LCD, size 65x33mm, resolution 128x64
Self regulating contrast with the temperature and with possibility of
manual correction.
Operating conditions
From -30°C to +70°C, 95% not condensing humidity
Stock conditions
From -35°C to +80°C
Size
141(L)x113(H)x39(P)mm
Weight
191g the only device
250G with connectors and fixing
Dimensions of the mounting
place
118x92mm
Protection degree
IP 65 external with mounted seal, IP20 internal
3.1
Mains/Bars and Genset
voltages
1Vrms
accuracy <1% F.S.
Current
Min. 0.1A (it depends on the CT ratio)
accuracy <1% F.S.
Mains/Bars and Genset
frequencies
0.1Hz ± 50ppm, 35ppm/C typical
Powers
Min. 0.1 kW/kVA/kvar (it depends on the CT ratio)
Power Factor
0.01
Energy
1 kWh/kvarh
Engine speed
1 rpm
Oil pressure
0.1bar (below 10bar)
Cooling liquid temperature
0.1°C
Fuel level
0.1%