12 

 

User’s Manual  

 

If active, they connect the input to ground otherwise they are open circuit. 

Terminal 

Output type 

Function 

JG  40 

Open 
collector, 
350mA. 

ENGINE RUNNING. Programmable output preset to signal an 
engine running status. 

JG  41 

Open 
collector, 
350mA. 

WARNINGS. Programmable output preset to signal the 
presence of one or more warnings. 

JG  42 

Open 
collector, 
350mA. 

ALARMS. Programmable output preset to signal the presence 
of one alarm or disable. 

JG  43 

Open 
collector, 
350mA. 

MAN-AUTO-TEST. Programmable output preset to signal the 
presence of one of the three listed mode (also the REMOTE 
START status is signaled). 

JG  44 

Open 
collector, 
350mA. 

AUTO-TEST. Programmable output preset to signal the 
presence of one of the two listed mode (also the REMOTE 
START status is signaled). 

JG  45 

Open 
collector, 
350mA. 

OUTPUT 45 

GENERATOR ALARM

. Programmable output 

preset to signal a block or disable dues to the generator. 

JG  46 

Open 
collector, 
350mA. 

OUTPUT 46 

SPEED ALARM.

 Programmable output preset to 

signal block dues to engine speed. 

JG  47 

Open 
collector, 
350mA. 

OUTPUT 47 

ENGINE ALARM.

 Programmable output preset to 

signal a block or disable dues to the engine. 

The following table lists the function that can be assigned to the programmable outputs. 

 

Code 

Description 

Not used 

Output reset pulse 

Glow-plugs preheater 

Fuel pump 

Load (power) level status 

Remote signal test running 

Remote signal mains OK 

Remote signal generator live 

Remote signal engine running 

Remote signal generator alarm 

10 

Remote signal engine alarm 

11 

Remote signal speed alarm 

12 

Remote signal fuel alarm 

13 

Remote signal contactors alarm 

14 

Gas valve 

15 

Monostable output 

16 

Stop solenoid 

17 

Remote signal or warnings 

18 

Remote signal or alarms 

19 

Remote signal MAN-AUTO-TEST 

20 

Remote signal AUTO-TEST 

21 

External horn 

22 

Remote signal configured by bits 

23 

Engine idle speed command 

 

Summary of Contents for DST4601

Page 1: ...Filename EAAM005709EN docx Rev 09 Date 06 05 2013 ID Document EAAM0057 Product DST4601...

Page 2: ...tputs 11 3 4 Engine input output terminals 13 3 5 Other connectors 13 3 5 1 JH Power Supply 13 3 5 2 JI RS232 13 3 5 3 JP and JR connector 13 4 Programming notice 14 4 1 Access code 14 4 2 How to modi...

Page 3: ...makes generation function impossible and causes the automatic generator shutdown after a proper cooling down cycle The word WARNING is used to indicate a warning that requires an operator action but...

Page 4: ...ttons Key position Function OFF RESET PROGRAM Gen set is disabled All the alarms are reset It is possible to gain access to programming function MAN Gen set is in manual mode AUTO TEST Gen set is in a...

Page 5: ...y or enables disables the change mode of a variable EXIT Brings up to the previous menu level Used together with the SHIFT pushbutton changes the fuel pump mode to manual enables disables the fuel pum...

Page 6: ...e active phase is indicated by the position of a dash on the fourth digit of FREQUENCY display dash in upper position for L1 L2 phases dash in middle for L2 L3 and dash in bottom for L3 L1 Mode is ind...

Page 7: ...ws to modify the value press ENTER to confirm or EXIT to abort To go back the previous menu press the EXIT pushbutton This mode shows by means of some different pages information about the genset oper...

Page 8: ...changed the displayed phase TEST ON or FLASHING if in TEST mode FUEL PUMP OFF fuel pump command in manual and inactive ON fuel pump command in automatic and inactive FLASHING fuel pump command in auto...

Page 9: ...le input preset to test command If driven and the key lock is in AUTO actives the TEST mode JA 07 INPUT 07 OIL PRESS ALARM Programmable input preset to a BLOCK for engine minimum oil pressure JA 08 IN...

Page 10: ...t preset to the HIGH FUEL LEVEL function The following functions can be assigned to the digital inputs Code Description 0 Not used 1 External warning 2 External disable 3 External block 4 External eng...

Page 11: ...minal Output type Function JD 21 Relay 1A N O OUTPUT 21 FUEL PUMP Programmable output preset to the function FUEL PUMP COMMAND JD 22 Relay 1A N O OUTPUT 22 FUEL ALARM Programmable output preset to the...

Page 12: ...ammable output preset to signal a block or disable dues to the generator JG 46 Open collector 350mA OUTPUT 46 SPEED ALARM Programmable output preset to signal block dues to engine speed JG 47 Open col...

Page 13: ...O NOT USE JF 33 Measure input OIL PRESSURE Input for oil pressure sensor VDO VEGLIA or optional 0 10V JF 34 Measure input W TEMPERATURE Input for coolant temperature sensor VDO VEGLIA or optional 0 10...

Page 14: ...n the menu included the password modify pages It s possible that after password input menu doesn t show all the allowed pages In this case press EXIT to go to previous menu and access again the menu a...

Page 15: ...amp identify each record The number is shown in the upper right position of multifunction display together with the total number of available records Consider that when the archive is full a new recor...

Page 16: ...keys to select LANGUAGE then press ENTER again At this point board will ask for the password If the keyed password is correct will be shown a page that allows selecting the operating language To make...

Page 17: ...t be removable without tools Safety EARTH connection must be made in a fixed way by means at least one of the dedicated terminals The generator and mains voltage lines connected to the measure inputs...

Page 18: ...18 User s Manual HOLE 5MM 240 80 80 260 70 EXAGONAL NUT 4MA SPRING WASHER 4 WASHER 4...

Page 19: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...

Reviews: