12
User’s Manual
If active, they connect the input to ground otherwise they are open circuit.
Terminal
Output type
Function
JG 40
Open
collector,
350mA.
ENGINE RUNNING. Programmable output preset to signal an
engine running status.
JG 41
Open
collector,
350mA.
WARNINGS. Programmable output preset to signal the
presence of one or more warnings.
JG 42
Open
collector,
350mA.
ALARMS. Programmable output preset to signal the presence
of one alarm or disable.
JG 43
Open
collector,
350mA.
MAN-AUTO-TEST. Programmable output preset to signal the
presence of one of the three listed mode (also the REMOTE
START status is signaled).
JG 44
Open
collector,
350mA.
AUTO-TEST. Programmable output preset to signal the
presence of one of the two listed mode (also the REMOTE
START status is signaled).
JG 45
Open
collector,
350mA.
OUTPUT 45
GENERATOR ALARM
. Programmable output
preset to signal a block or disable dues to the generator.
JG 46
Open
collector,
350mA.
OUTPUT 46
SPEED ALARM.
Programmable output preset to
signal block dues to engine speed.
JG 47
Open
collector,
350mA.
OUTPUT 47
ENGINE ALARM.
Programmable output preset to
signal a block or disable dues to the engine.
The following table lists the function that can be assigned to the programmable outputs.
Code
Description
0
Not used
1
Output reset pulse
2
Glow-plugs preheater
3
Fuel pump
4
Load (power) level status
5
Remote signal test running
6
Remote signal mains OK
7
Remote signal generator live
8
Remote signal engine running
9
Remote signal generator alarm
10
Remote signal engine alarm
11
Remote signal speed alarm
12
Remote signal fuel alarm
13
Remote signal contactors alarm
14
Gas valve
15
Monostable output
16
Stop solenoid
17
Remote signal or warnings
18
Remote signal or alarms
19
Remote signal MAN-AUTO-TEST
20
Remote signal AUTO-TEST
21
External horn
22
Remote signal configured by bits
23
Engine idle speed command