SIAD ESA E7014 Manual Download Page 17

 

    E7014 
 

 

17 

 
 
 

Postpurge time 

0 ÷ 255 

Time  of  furnace  chamber  purging  after  shutoff  or  waiting  before  next 
burner ignition (air valve opening in case of applications with air valve 
control).  During  this  phase  the  device  doesn’t  accept  any  external 
command. 
The  function  “Postpurge  flex”  defines  the  minimum  interval  of  time 
between two ignition attempts. 

Cycle start 

Autostart 

The  ignition  cycle  starts  automatically  at  power  supply  (except  for 
cases  of  burner’s  lockout  before  shutoff).  This  type  of  setting  is 
suitable for burner control via the device power supply.  

Standby 

The ignition cycle doesn’t start automatically at power supply (waiting 
for  local  or  remote  command).  This  type  of  setting  is  suitable  for 
burner control via the serial communication.  

1° stage gas 

outlet type 

Intermittent 

The 1

st

 stage gas remains ON also during the 2

nd

 stage gas until the 

simultaneous shutoff of both valves. 
This  setting  is  allowed  only  for  ESTRO-B  release,  the  parameter  is 
locked for ESTRO-A, ESTRO-C and ESTRO-Q (only 1

st

 stage gas.) 

Interrupted 

The  1

st

  stage  gas  is  turned  OFF  during  the  2

nd

  stage  gas  when  the 

second safety time or “Regulation delay time” (2

nd

 stage stabilization) 

is  exceeded.    This  setting  is  allowed  only  for  ESTRO-B  release,  the 
parameter is locked for ESTRO-A, ESTRO-C and ESTRO-Q (only 1

st

 

stage gas.) 

Daily shut off 

Inhibited 

The device doesn’t turn OFF automatically each 24 hours for self-
diagnosis. This selection is allowed only for combustion plants with 
several burners installed on the same furnace chamber, nevertheless 
the accomplishment of the self-diagnosis shutoff have to be controlled 
by the overall control system. In case this function is enabled, the 
device comply only EN746-2. 

Enable 

The  device  turns  OFF  automatically  each  24  hours  for  self-diagnosis 
and flame detection probe test.  

Air pressure 

switch 

Inhibited 

The  air  pressure  switch  connected  to  the  expansion  card  is  not 
verified.  

Waiting 

A missing signal from the air pressure switch implies: 

-

 

during the purging phase sets at zero the countdown; 

-

 

(with continuous air control) burner shutoff waiting the new signal 
presence (automatic restart) .  

-

 

(with  discontinuous  or  pulse  air  control,  and    burner  lights  the 
status will change for disabling of air) 

Lockout 

A missing signal from the air pressure switch implies: 

-

 

during the purging phase sets at zero the countdown; 

-

 

(with continuous air control) burner shutoff waiting the new signal 
presence (reset requested for restart).  

-

 

(with  discontinuous  or  pulse  air  control,  and  burner  lights  the 
status will change for disabling of air) 

Summary of Contents for ESA E7014

Page 1: ...nstallation on burner proximity provided the environment temperature will remain below 60 C APPLICATIONS One or two stages pilot and main discontinuous burners Flame detection by means of rod unirod a...

Page 2: ...nt per output signals total 4 A per 10 sec min Load protection fuse 4 A fast Device protection fuse 1 A non replaceable Supply Voltage expansion card EXP 2 and EXP 4 24 Vac 115 Vac 230 Vac Power Absor...

Page 3: ...f the air valve operation ESA ESTRO B two stages burners 1st pilot 2nd main The configuration software sets the operation of the pilot burner 1st stage gas in continuous or discontinuous mode ESA ESTR...

Page 4: ...tly provided with ECS serial communication interface in order to allow the remote burner control through ECS or Modbus RTU protocols The serial communication allows the complete control of the combust...

Page 5: ...ing composition ready to seat the ignition transformer and the output wires for external connections Dedicated Expansion cards can be connected to each release of ESA ESTRO in order to implement addit...

Page 6: ...298 as certificate I7800 issued by notify body 0694 ESA ESTRO is in accordance to European Union directives Directive on appliances burning gaseous fuels 90 396 CEE Machine directive 2006 42 CEE Low v...

Page 7: ...own with expansion cards in case the parameter Air damper is configured as Local o Remote FIXED Purge or waiting time before burner ignition For applications with controlled cooling slope only the air...

Page 8: ...utton during the normal operation stage The device holds the burner in OFF mode waiting for a new start signal BLINKING Lockout due to a signal of illegal flame presence before the burner ignition or...

Page 9: ...uld be related to an electrical connection interruption to the failure of one of the ignition devices or to a protection fuse failure BLINKING Lockout due to a malfunction of the flame detection probe...

Page 10: ...to be sent back to the manufacturer for inspection FIXED Malfunction due to short circuit of the microprocessors pins In order to reset the alarm cut off the electrical supply to the device for few s...

Page 11: ...utton operation according its application s requirement see chapter Configuration The push button may execute the manual operations of unlocking and shutoff only manual unlocking only manual shutoff a...

Page 12: ...nd oil fired burners in different modes according the process parameters set see chapter Configuration Hereinafter its main actions are described BURNER IGNITION CYCLE The scheme describes the burner...

Page 13: ...cycle execution when ESA ESTRO is in standard version without the EXP 2 expansion card OPERATION AT POWER SUPPLY The followings scheme describe the ESA ESTRO actions at power supply according the conf...

Page 14: ...E7014 14 Standby ILLEGAL FLAME PRESENCE The scheme describes the ESA ESTRO actions in case of illegal flame signal before burner ignition or after shutoff...

Page 15: ...the actions in case of failed ignition attempt at 1st gas stage FLAME SIGNAL LOST The scheme describes the actions in case of flame signal lost during the normal operation stage and in case of settin...

Page 16: ...Address Node 0 9 and A Z capital Address Segment identifies the device for serial communication Adopting ECS protocol defoines the device unity inside a zone or belonging group Adopting Modbus RTU def...

Page 17: ...eeded This setting is allowed only for ESTRO B release the parameter is locked for ESTRO A ESTRO C and ESTRO Q only 1st stage gas Daily shut off Inhibited The device doesn t turn OFF automatically eac...

Page 18: ...lled Enable The device controls the installed expansion cards this setting is required in case EXP 2 and EXP 4 are installed Behavior Action at flame loss Lockout In case the signal of flame presence...

Page 19: ...t disabled it leads the burner shutoff Air valve on off The digital input controls the air valve as alternative to the serial commands with active input and 1st stage gas ON the device allows air valv...

Page 20: ...EXP 2 Postpurge flex Inhibited The device starts the Post purge time countdown from the burner shutoff or lockout Enable The device starts the Post purge time countdown from the burner ignition Lo str...

Page 21: ...pecific norm in order to define the proper parameters related to each industrial application adopting values that don t compromise the process safety In case the setting parameters are not in complian...

Page 22: ...than how indicated otherwise the ignition transformer must be located near the burner The HV cable must be laid far from power supply cables and not in metallic conduit the best is the cable free in a...

Page 23: ...id gas valve by other devices relay PLC that receive the signal by the ESA ESTRO don t are permitted In case of noises during the ignition phase due to the presence of others electrical equipments it...

Page 24: ...IPTION L Power supply phase 6 Air valve neutral N Power supply neutral 7 Ignition transformer phase 1 Lockout signal output phase 8 Ignition transformer neutral 2 Digital input phase 9 Detection rod s...

Page 25: ...ockout signal output phase 6 2nd stage gas valve neutral B Digital input phase 7 Ignition transformer phase 1 Power supply phase 8 Ignition transformer neutral 2 Power supply neutral 9 Detection rod s...

Page 26: ...signal output phase 6 Burner ON free contact output NO B Digital input phase 7 Ignition transformer phase 1 Power supply phase 8 Ignition transformer neutral 2 Power supply neutral 9 Detection rod sig...

Page 27: ...N 1st stage gas valve neutral N Power supply neutral T Ignition transformer phase Not connected N Ignition transformer neutral Positive input for serial communication F Detection rod signal from trans...

Page 28: ...ch input phase 12 Negative input for serial communication 19 Air damper limit switch inputs common neutral 13 Temperature regulation enabling output phase 20 Thermostat start stop input phase 14 Air d...

Page 29: ...formed holes No 6 11 POS DESCRIPTION A Attacchi per fissaggio trasformatore C Available Non utilizzato D Available Non utilizzato E E Available Non utilizzato F Terminal grounding G G fixing holes for...

Page 30: ...Pre wiring Esa Trafo coupled box With expansion Exp 3 C High temperature function R 4 minute 4M from 0 to 99 seconds Enable F Reaction time at flame loss 5 10 Version Daily check shout off Comunicatio...

Reviews: