background image

PLUMBING

• 

SHURflo swivel hex/barb fittings provide easy removal if maintenance or access is required. The
fittings are designed with a "taper-seal", creating a water tight connection when 

hand-tightened

¼

turn after contact. Always secure barb tubing connections with properly sized stainless steel clamps to 
prevent leaks. For connecting to the pumps 1/2" threaded ports SHURflo supplies taper-seal swivel-
barb fittings for various tubing sizes.

*

 Included with retail Baitmaster pump kits 

• 

Inlet tubing (1/2"I.D. min.) from the sea-cock valve to the pump should be rated for vacuum. If rigid 
tubing or pipe is utilized, SHURflo recommends the inlet port be plumbed with a minimum of 1 ft.[.3

M

]

of flexible vacuum rated tubing. Standard garden hose is not suitable as inlet tubing as it may collapse 
under vacuum, reducing water flow.

• 

The pump outlet port 

should not

 be connected to rigid (plastic) pipe. Normal oscillation of the pump 

may transmit through rigid plumbing causing noise and possibly loosen or crack components. A
minimum of 1 ft.[.3

M

] length of flexible high pressure tubing is suggested. Avoid any sharp radius in 

tubing that may kink over time. Route tubing away from any heat (exhaust manifolds etc.) and fasten 
securely.

RAW WATER STRAINER

A bait system is only as dependable as the water available to pump. A strainer with adequate capacity to 
trap debris 

must

 be part of the system. Using #50 mesh or larger provides sufficient capacity under 

most conditions. The interval for cleaning will be determined by the amount of debris encountered.
Check the strainer before and after each use. 

Failure due to debris in the pump will not be covered 

under warranty.

CAUTION:

The strainer 

must

 be mounted above the outside water line to prevent water from siphoning during 

cleaning, without closing the sea-cock valve. Mount the strainer where it can be inspected and 
cleaned easily.

NOTES & CAUTIONS

• 

To prevent cavitation, through hull fittings should be located at least 12 in. off the center line of the
water pick-up for the motor.

• 

The through hull fitting should have a sea-cock valve to shut-off in case of an emergency.

• 

Double clamp all tubing connections that are below the water line.

• 

Always use high quality non-corrosive fittings, valves, and hardware to assure long term reliability.

• 

Electrical connections should be soldered and insulated to prevent shorts and corrosion. Wiring should 
be routed away from areas prone to water, excess moisture, and heat. Properly seal all pipe threads 
before the strainer to prevent unforeseen leaks.

Never

 use Teflon tape or sealing compounds on pump 

threads. Sealer may enter the pump causing a failure not covered under warranty.

WINTERIZING

If water is allowed to freeze in the system, serious damage to the plumbing and pump may occur.  Failures of 
this type will void the warranty.  The best guarantee against damage is to completely drain the system as
follows:

1.

Turn power 

OFF

 to the pump. Close the sea-cock valve at the through-hull fitting. All water in the inlet tubing 

should be drained.

2.

Remove both inlet/outlet port connections at the pump and drain the tubing.

3.

Turn the pump 

ON

 and allow water inside the pump to be purged. 

It is recommended that the pump's inlet/outlet port not be reconnected.

4.

 Make a note at both the sea-cock valve and bait tank that the "Plumbing is Disconnected".

GENERAL SAFETY PRECAUTIONS

• 

When the vessel is not in use, the main power switch and sea-cock valves should be 

OFF

.  However, if 

left afloat the bilge pump should still have power. Never operate the engine or electrical equipment if 
fuel vapor is detected until the source is located and/or properly vented.

911-738 Rev F

Page 3 of 5

Reviews: