26
Display
Name, Function, Setting range
Default value
Output 100% value
9999 (SE2U, SE2A, SE2V, SE2P,
SE1U, SE1A, SE1V, SE1P,
SE1D, SE1D-F, SEWU,
SEWD)
1370 (SE2E, SE1E)
850
(SE2R, SE1R)
IN
OUT
• Thermocouple, RTD input:
Sets the temperature at 100% output.
Setting range: Output 0% value to Input range high limit value
• DC current, voltage input or SE1D, SE1D-F, SE2P:
Sets the value (indicated on the Input display) at 100% output.
• Setting range: Output 0% value to 9999
Filter time constant
0.0 seconds
IN
OUT
Sets the filter time constant.
Reduces input fluctuation caused by noise.
Setting range: 0.0 to 10.0 seconds
Sensor correction
0 (SE2U, SE2A, SE2V, SE2P,
SE1U, SE1A, SE1V, SE1P,
SE1D, SE1D-F, SEWU, SEWD)
0.0 (SE2E, SE2R, SE1E, SE1R)
IN
OUT
Sets the sensor correction value.
Input value = Current input value + (Sensor correction value)
Setting range:
Thermocouple, RTD input: -100.0 to 100.0 ( )
DC current, voltage, potentiometer input, current loop supply: -1000 to 1000
Output type
4 to 20mA DC
Selects the output type.
For the SEW , this is Output 1 type.
IN
OUT
: 4 to 20mA DC
: 0 to 20mA DC
: 0 to 12mA DC
: 0 to 10mA DC
: 1 to 5mA DC
: 0 to 1V DC
: 0 to 5V DC
: 1 to 5V DC
: 0 to 10V DC
Output Normal/Reverse
Normal
IN
OUT
Selects either Output Normal mode (0.0 to 100.0%) or Reverse mode (100.0
to 0.0%), corresponding to the input.
: Normal
: Reverse
Burnout
Upscale
IN
OUT
Selects Upscale (110.0%) or Downscale (-10.0%) output when input
indicates burnout.
Available for thermocouple, RTD input.
: Upscale
: Downscale