24
6.3 Setup of the unit
6.3.1 Function group
For the SE2 , this is CH1 function group.
For the SEW , this is Input/Output 1 function group.
To enter the function group, follow the procedures below.
(1)
Press the
key in the RUN mode until the left characters appear.
(2)
Press the
key. The Input type selection item appears.
Set up the unit referring to the explanation of each item.
Display
Name, Function, Setting range
Default value
Input type
DC voltage input
IN
OUT
Selects an input type.
Only available for the SE2U, SE1U, SEWU.
: Thermocouple input
: RTD input
: DC current input
: DC voltage input
Thermocouple input range
K: -200 to 1370
Selects thermocouple input range.
Available for thermocouple input
: K
: K (*)
: K (*)
: J
: J (*)
: J (*)
: R
: S
: B
: E
: T (*)
: N
: PL-
: W5Re/W26Re
: W3Re/W25Re
-200 to 1370
-200 to 200
0 to 400
-200 to 1000
-200 to 200
0 to 400
-50 to 1760
-50 to 1760
0 to 1820
-200 to 800
-200 to 400
-200 to 1300
0 to 1390
0 to 2315
0 to 2315
IN
OUT
: K
: K (*)
: K (*)
: J
: J (*)
: J (*)
: R
: S
: B
: E
: T (*)
: N
: PL-
: W5Re/W26Re
: W3Re/W25Re
-328 to 2498
-328 to 392
32 to 752
-328 to 1832
-328 to 392
32 to 752
-58 to 3200
-58 to 3200
32 to 3308
-328 to 1472
-328 to 752
-328 to 2372
32 to 2534
32 to 4199
32 to 4199