Alarm 1 Hold function
selection
0000H: Alarm Not holding
0001H: Alarm Holding
0000H: Alarm
Not holding
Alarm 2 Hold function
selection
0000H: Alarm Not holding
0001H: Alarm Holding
0000H: Alarm
Not holding
Alarm 3 Hold function
selection
0000H: Alarm Not holding
0001H: Alarm Holding
0000H: Alarm
Not holding
Alarm 4 Hold function
selection
0000H: Alarm Not holding
0001H: Alarm Holding
0000H: Alarm
Not holding
Input type selection (*1)
0000H: K
[-200 to 1370 ]
0001H: K
[-199.9 to 500.0 ]
0002H: J
[-200 to 1000 ]
0003H: R
[0 to 1760 ]
0004H: S
[0 to 1760 ]
0005H: B
[0 to 1820 ]
0006H: E
[-200 to 800 ]
0007H: T
[-199.9 to 400.0 ]
0008H: N
[-200 to 1300 ]
0009H: PL-
[0 to 1390 ]
000AH: C(W/Re5-26) [0 to 2315 ]
000BH: Pt100
[-199.9 to 850.0 ]
000CH: JPt100 [-199.9 to 500.0 ]
000DH: Pt100
[-200 to 850 ]
000EH: JPt100
[-200 to 500 ]
000FH: K
[-320 to 2500 ]
0010H: K
[-199.9 to 932.0 ]
0011H: J
[-320 to1800 ]
0012H: R
[0 to 3200 ]
0013H: S
[0 to 3200 ]
0014H: B
[0 to 3300 ]
0015H: E
[-320 to 1500 ]
0016H: T
[-199.9 to 750.0 ]
0017H: N
[-320 to 2300 ]
0018H: PL-
[0 to 2500 ]
0019H: C (W/Re5-26) [0 to 4200 ]
001AH: Pt100
[-199.9 to 999.9 ]
001BH: JPt100 [-199.9 to 900.0 ]
001CH: Pt100
[-300 to 1500 ]
001DH: JPt100
[-300 to 900 ]
001EH: 4 to 20mA DC
[-1999
to
9999]
001FH: 0 to 20mA DC
[-1999
to
9999]
0020H: 0 to 1V DC [-1999 to 9999]
0021H: 0 to 5V DC [-1999 to 9999]
0022H: 1 to 5V DC [-1999 to 9999]
0023H: 0 to 10V DC [-1999 to 9999]
0000H:
K [-200 to 1370 ]
PV filter time constant
setting
0.0 to 10.0s
0.0s (*2)
OUT1 high limit setting
OUT1 low limit value to 100%
(A/M: OUT1 low limit value to 105%)
100%
OUT1 low limit setting
0% to OUT1 high limit value
(A/M: -5% to OUT1 high limit value)
0%
(*1) For DC current input, connect 50 shunt resistor (sold separately).
(*2) If setting value is too large, it affects control result due to the delay of the response.