20H/50H
06H/03H
0026H: A2 action hysteresis setting
Setting value
20H/50H
06H/03H
0027H: Not used
20H/50H
06H/03H
0028H: Not used
20H/50H
06H/03H
0029H: A1 action delayed timer setting
Setting value
20H/50H
06H/03H
002AH: A2 action delayed timer setting
Setting value
20H/50H
06H/03H
002BH: Not used
20H/50H
06H/03H
0036H: Not used
20H/50H
06H/03H
0037H: OUT/OFF selection
0: OUT
1: OFF
20H/50H 06H/03H
0038H:
Auto/Manual
control 0:
Automatic
control
1: Manual control
20H/50H
06H/03H
0039H: Manual manipulated variable
Setting value
20H/50H
06H/03H
003AH: Not used
20H/50H
06H/03H
003FH: Not used
20H/50H 06H/03H
0040H:
A1 action Energized/Deenergized
0: Energized 1: Deenergized
20H/50H 06H/03H
0041H:
A2 action Energized/Deenergized
0: Energized 1: Deenergized
20H/50H
06H/03H
0042H: Not used
20H/50H
06H/03H
0043H: Not used
20H/50H
06H/03H
0044H: Input type selection
0: K [-200 to 1370 ]
1: K [-199.9 to 400.0 ]
2: J
[-200 to 1000 ]
3: R [0 to 1760 ]
4: S [0 to 1760 ]
5: B [0 to 1820 ]
6: E [-200 to 800 ]
7: T [-199.9 to 400.0 ]
8: N [-200 to 1300 ]
9: PL-
[0 to 1390 ]
10: C (W/Re5-26) [0 to 2315 ]
11: Pt100 [-199.9 to 850.0 ]
12: JPt100 [-199.9 to 500.0 ]
13: Pt100 [-200 to 850 ]
14: JPt100 [-200 to 500 ]
15: K [-320 to 2500 ]
16: K [-199.9 to 750.0 ]
17: J
[-320 to 1800 ]
18: R [0 to 3200 ]
19: S [0 to 3200 ]
20: B [0 to 3300 ]
21: E [-320 to 1500 ]
22: T [-199.9 to 750.0 ]
23: N [-320 to 2300 ]
24: PL-
[0 to 2500 ]
25: C (W/Re5-26) [0 to 4200 ]
26: Pt100 [-199.9 to 999.9 ]
27: JPt100 [-199.9 to 900.0 ]
28: Pt100 [-300 to 1500 ]
29: JPt100 [-300 to 900 ]
30: 4 to 20mA DC[-1999 to 9999]
31: 0 to 20mA DC[-1999 to 9999]
32: 0 to 1V DC [-1999 to 9999]
33: 0 to 5V DC [-1999 to 9999]
34: 1 to 5V DC [-1999 to 9999]
35: 0 to10V DC [-1999 to 9999]
20H/50H
06H/03H
0045H: Direct/Reverse action selection
0: Heating (Reverse action)
1: Cooling (Direct action)
20H/50H
06H/03H
0046H: Not used
20H/50H
06H/03H
0047H: AT bias setting
Setting value
20H/50H
06H/03H
0048H: ARW (anti reset windup) setting
Setting value
20H/50H
06H/03H
006FH: Key LOCK selection
0: Key enabled 1: LOCK
50H 03H
0070H:
Key operation change flag clearing
0: No action 1: All clearing
20H
06H
0080H: PV (input) value reading
Present PV (input) value