35
(*7) If 00FFH (Key operation change flag clearing) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol)
will be returned.
If any value except 0001H (Clear key operation change flag) is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus
protocol) will be returned.
(*8) Contents of error code are shown below.
Error Code
Contents
Error 01
Internal non-volatile IC memory is defective.
Error 02
Data writing (in non-volatile IC memory) error when power failure occurs.
Error 05
Overscale.
PV has exceeded Input range high limit value (Scaling high limit value for DC voltage, current inputs).
Error 06
Underscale.
PV has dropped below Input range low limit value (Scaling low limit value for DC voltage, current inputs).
Error 07
Input burnout or disconnection.
Input value is outside of the Indication range and control range.
Error 10
Hardware malfunction
Error 20
AT or AT on startup has not been completed even if approx. 4 hours has elapsed since starting.
For AT on startup, PV slope and delay time cannot be measured normally for P, I, D calculation.
(*9) If B13 or B14 is “1: ON”, B11 will also be “1: ON”.
(*10) Data item
16
3
digit:
0: Fixed value control, 1: Program control
16
2
to 16
0
digits: Data item code (serial number) for each step
(*11) Step 1 SV (1000H) corresponds to SV1 (0001H) and SV1 (000EH).
(*12) Step 2 SV to Step 4 SV (1003H, 1006H, 1009H) correspond to SV2 to SV4 (000FH, 0010H, 0011H).
(*13) For TS1 OFF time (0073H), TS1 ON time (0074H), TS2 OFF time (0076H), TS2 ON time (0077H), and Steps 1 to 9 time (1001H, 1004H,
1007H, 100AH, 100DH, 1010H, 1013H, 1016H, 1019H):
Calculate the step time using the smaller time unit at 006DH (Step time unit), then convert it to hexadecimal numbers.
Use hexadecimal numbers for settings as follows.
Setting range: 00:00 to 99:59 (0 to 5999)
(e.g.) When ‘Hours:Minutes’ is selected in [Step time unit].
1:00
1 x 60 + 00=60
003CH
1:30
1 x 60 + 30=90
005AH
FFFFH: The step time is held, and Fixed value control is performed.