29
Shinko
Command
Type
Modbus
Function
Code
Data Item
Data
20/24/50/54H
03/06/10H
002CH Reserved
(*2)
:
:
:
:
20/24/50/54H
03/06/10H
003BH Reserved
(*2)
20/24/50/54H
03/06/10H
003CH OUT1 proportional band
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
003DH Integral time
Set value
20/24/50/54H
03/06/10H
003EH Derivative time
Set value
20/24/50/54H
03/06/10H
003FH ARW
Set value
20/24/50/54H
03/06/10H
0040H Manual reset
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0041H OUT1 proportional cycle
Set value
20/24/50/54H
03/06/10H
0042H OUT1 ON/OFF hysteresis
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0043H OUT1 high limit
Set value
20/24/50/54H
03/06/10H
0044H OUT1 low limit
Set value
20/24/50/54H
03/06/10H
0045H OUT1 rate-of-change
Set value
20/24/50/54H
03/06/10H
0046H OUT2 cooling method
0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling
20/24/50/54H
03/06/10H
0047H OUT2 proportional band
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0048H OUT2 proportional cycle
Set value
20/24/50/54H
03/06/10H
0049H OUT2 ON/OFF hysteresis
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
004AH OUT2 high limit
Set value
20/24/50/54H
03/06/10H
004BH OUT2 low limit
Set value
20/24/50/54H
03/06/10H
004CH Overlap band/Dead band
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
004DH Direct/Reverse action
0000H: Reverse (Heating) action
0001H: Direct (Cooling) action
20/24/50/54H
03/06/10H
004EH Set value lock
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
0004H: Lock 4
0005H: Lock 5
20/24/50/54H
03/06/10H
004FH Sensor correction coefficient
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0050H Sensor correction
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0051H PV filter time constant
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0052H Response delay time
Set value
20/24/50/54H
03/06/10H
0053H SVTC bias
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0054H External setting input high limit
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0055H External setting input low limit
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0056H Remote bias
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0057H SV Rise/Fall rate start type
0000H: SV start
0001H: PV start
20/24/50/54H
03/06/10H
0058H SV rise rate
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
0059H SV fall rate
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
005AH Indication when control output
OFF
0000H: OFF indication
0001H: No indication
0002H: PV indication
0003H: PV indi Any Alarm
active
20/24/50/54H
03/06/10H
005BH AT bias
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
005CH Output status when input
errors occur
0000H: Output OFF
0001H: Output ON
20/24/50/54H
03/06/10H
005DH Auto/Manual after power ON
0000H: Automatic control
0001H: Manual control