Section 3 Installation
VM-21P 3-Wire LVDT Signal Conditioner Instruction Manual
- 26 -
3.3.3 Connecting the power supply
Connect the power supply as explained below.
Point
600V vinyl code (IV) stranded wire (JIS C 3307, or similar) with a nominal
conductor sectional area of 1.25 to 2.0mm
2
, or similar product, is
recommended for electric wire.
When using a signal conditioner socket
When using a backplane unit
<24V DC power supply specifications>
Connect wires as shown in figure when the redundant is necessary for the power supply.
But,there is not priority to
①
,
②
.
Connect either
①
or
②
with power supply when the redundant is not necessary .
<100 to 240V AC/DC power supply specifications>