②
Adjust the current amperage by the current adjust dial, per the table below.
Welding Current at the dial position
Position
Freq
MIN
1 2 3 4 5
MAX
Eco 40
60
100
140
180
220
240
50Hz
90
120
190
250
320 360 380
1 Person
Single
Use
60Hz
110
140
200
260
320 380 400
50Hz
50
70 100
130
160 180 190
2 Persons
Dual
Use
60Hz
55
70 110
140
170 200 210
The values shown in the table are for reference only. The length and the ambient
temperature affect the value.
When the remote control box is used, the values change to some degree.
9. Generator Operation
9-1 Output Range
(1) 3-Phase 380-415V Output (3-Phase 4-Wire)
Maximum output from the terminals is 15KVA.
(2) 1-Phase 380-415V Output Terminals
1-Phase 380-415V Output is available, using the output terminals. Maximum output
available for the one set of the terminals is 9kVA but the total output for 3 sets is
12KVA, which please note and care. You should use the 3 sets wires evenly as
much as possible.
(3) 1-Phase 220-240V Output Receptacles
1-Phase 220-240V Output is available through 2 receptacle sets.
Maximum output is 3kVA for 2 receptacle sets.